Setting the mode used for operation
Set basic operation for Hybrid GHP/EHP control and set demand control.
1
Touch [System Settings] in "Settings".
The "System settings" screen is displayed.
z
1
2
Touch [Hybrid GHP/EHP settings].
Enter the identification number (password level 1 or 2) and
z
the "Hybrid GHP/EHP settings" screen is displayed.
3
Touch [Basic settings].
The "Basic settings" screen is displayed.
z
2
3
4
Select the Hybrid GHP/EHP control
mode setting.
Item
Cost priority
control
Energy priority
control
EHP priority
control
GHP priority
control
5
Select the demand setting.
Item
Not set
EHP demand
GHP demand
175
[Basic settings]
4
Explanation
Control so that the power/gas usage
charges are kept to a minimum based
on the unit prices set in the "Cost
settings" screen.
Control so that the energy consumed is
kept to a minimum.
The system operates so that the EHP
side is prioritised, with GHP operating
only when capacity is insufficient.
The system operates so that the GHP
side is prioritised, with EHP operating
only when capacity is insufficient.
5
Explanation
Demand control is not performed.
GHP takes some of the load from EHP
according to the demand level.
GHP demand control instructions are
issued according to the demand level.
The instruction value can be freely
changed in the "Gas demand settings"
screen.