Safety Precautions
Please Read Before Starting
This controller must be installed by the sales dealer or installer.
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certifi ed dealer
for additional instructions.
This symbol refers to a hazard or unsafe practice
WARNING
which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe
CAUTION
practice which can result in personal injury
or product or property damage.
 We assume no responsibility for accidents or damages
resulting from methods other than those described in the
installation instructions or methods without using specifi ed
parts. Malfunctions that occurred due to the unauthorised
installation methods are not covered by the product warranty.
 This controller shall be installed in accordance with local
codes.
 After the installation is complete, perform test operation to
confi rm that no abnormality is present.
 Read the installation instructions of devices to be connected as well.
 When relocating or repairing this controller, provide the
Installation Instructions to the servicing personnel.
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
ONLY A QUALIFIED, EXPERIENCED
ELECTRICIAN SHOULD ATTEMPT TO
WIRE THIS SYSTEM.
 This controller is strongly recommended to be installed
with Earth Leakage Circuit Breaker (ELCB) or Residual
Current Device (RCD).
Otherwise, it may cause electrical shock and fi re in
case of equipment breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be
incorporated in the fi xed wiring in accordance with the
wiring regulations. The Earth Leakage Circuit Breaker
Specifi cations
Model No.
CZ-256ESMC2U
Dimensions
9-29/64 × 11-1/32 × (0-25/32 + 2-9/16) in.
[H × W × D]
(240 × 280 × (20 + 65) mm)
Weight
5 lbs. (2.7 kg)
Temperature/
32 °F to 104 °F (0 °C to 40 °C) / 20 % to 80 %
Humidity range
(no condensation) Indoor use only.
Rated voltage/
AC24 V 60 Hz 1-PH
Rated frequency
Power consumption Max. 20 W
*1: The maximum number of connectable units is shown below.
• When using only this unit: 128 indoor units and 60 outdoor units
• When connecting a Communication Adaptor: 256 indoor units and 120 outdoor units
Panasonic Corporation
1006 Kadoma, Kadoma City, Osaka, Japan
85464369912010
WARNING
Panasonic Corporation
http://www.panasonic.com
Installation Instructions
Intelligent Controller
Model No.
(ELCB) must be an approved 10 A, having a contact
separation by 0-1/8 in. (3 mm) in all poles.
 Provide a power outlet to be used exclusively
for this controller.
 Turn off the circuit breaker of the controllers
before installation.
 Do not supply power to the controller until all
wiring is completed or reconnected and checked.
 Fix the power supply wiring securely with the
clamper so that the power supply terminal board is
free of tension (external force) when pulled. Loose
connection of the terminal board may cause fi re.
 Select an installation location which is rigid and
strong enough to support or hold the controller,
and select a location for easy maintenance.
 This product must not be modifi ed or
disassembled under any circumstances.
Modifi ed or disassembled controller may
cause fi re, electric shock or injury.
 Do not clean inside the controller by users.
Engage authorized dealer or specialist for cleaning.
 Do not operate with wet hands.
 Ground yourself to discharge static electricity
before performing any wiring.
 Do not use the controller at the following locations.
• Areas where leakage of fl ammable gas may be expected
• Places where large amounts of oil mist exist
• Locations where external air may enter the room
directly (This may cause "condensation")
• Locations where high-frequency emissions are generated
• Locations where voltage fl uctuation frequently occurs
 Do not wash with water.
± 30 seconds/month (at normal temperature 77 °F
Precision
(25 °C)) * Adjust periodically.
Clock
Holding
100 days (at normal temperature 77 °F (25 °C) with full charge)
time
* Approx. 8 hours are required for full charge.
Up to 100 units of the combined total of the
Number of
following
connectable
• Indoor unit - Up to 64 units*
units per link
• Outdoor unit - Up to 30 units
*1
• Central control device - Up to 10 units
*2: The number of indoor units includes the
Interface Adaptor.
CZ-256ESMC2U
CAUTION
2
CV6233334110
H0916-0

Advertisement

loading

Summary of Contents for Panasonic CZ-256ESMC2U

  • Page 1 Installation Instructions Intelligent Controller CZ-256ESMC2U Model No. Safety Precautions Please Read Before Starting (ELCB) must be an approved 10 A, having a contact This controller must be installed by the sales dealer or installer. separation by 0-1/8 in. (3 mm) in all poles.
  • Page 2 Installation Precautions Supplied accessories < >: Number of pieces Screw <4> Washer <4>  Installation Location (M4×10)  Avoid the following locations for installation. Nut <4> Clamper <4> • Under direct sunlight (M4) • Location near heat source • Location where the controller will be splashed with water or affected by dampness or humidity Operating Instructions and License List (DVD), •...
  • Page 3 Preparations for Wiring  Power Supply Wiring  Communication Adaptor Control Wiring • Power supply voltage : AC24 V 60 Hz 1-PH (When connecting a Communication Adaptor) • Voltage fl uctuation : ±10 % or less  Polarity (+/-) present •...
  • Page 4  Refer to “Quick Reference” and check the following. • Check and confi rm the connection confi guration. • Check if the clock setting and the number of connected units are correctly displayed. © Panasonic Corporation 2016 Printed in Japan...