en | Troubleshooting
RPS cannot perform remote
programming and control
Occasionally abnormal
communication in use of
Contact ID/personal
telephone alarm
No response from the keypad
and the alarm siren
(disabled) when an alarm is
triggered by the zone
The AMAX panel cannot send
any reports (programmed to
send reports to receiver)
A-LINK cannot be connected
with ITS- DX4020-G
9.2
Trouble Fault Inquiry
Fault Inquiry
Faults and tampers can be displayed via the fault analysis function. For more information refer
to System View, page 74.
The following faults and tampers are possible:
Lit number indicators
First
1
1
1
1
1
1
2015.05 | 06 | F.01U.309.277
All manuals and user guides at all-guides.com
–
–
–
–
–
–
–
Description of the fault or tamper
Second
Third
Accessory module failure
1
Network/IP module 1 failure
1
1 - 2
Network/IP module 1 - 2 failure
2
Output expansion module failure
2
1 - 2
Output expansion module 1 – 2 fault
3
Input expansion module failure
Installation Manual
Both addresses 0144
and 0145 are set to 0
Extension system is used
in the telephone network
The telephone network
support ADSL as well
The zone silent alarm is
enabled
The transmission format
of the receiver is
programmed to 0 = not
used
The parameters of
DX4020-G module are
not properly set.
The option Specific
network is not selected
for an IP remote
connection if a DX4020-
G module is used.
AMAX panel
–
Program the address
0144 to a number from 1
to 15. Program the
address 0145 to 1
–
Add dial delay in
programming
–
Connect the system after
the ADSL filter
–
Disable the zone silent
alarm
–
Program the
transmission format of
the receiver to 1 or 3
–
Recommend to set the
parameter ACK TIMEOUT
of DX4020-G module to
the maximum (600) and
set TRANSMIT BUFFER
LIFE TIME to the
maximum (120)
–
Select the option
Specific network for an
IP remote connection if a
DX4020-G module is
used.