• To enable the control method and the control mode selected in Pr.800 (Pr.451), the condition to start operation must be
satisfied as shown in the following table. Otherwise the operation does not start due to the setting error (SE) alarm when
the start signal is input.
Pr.800
Pr.451
setting
setting
0
1
Vector control
2
9
Vector control test operation
Real sensorless vector control /
10
PM sensorless vector control
11
Real sensorless vector control
12
19
PM sensorless vector control test operation
Advanced magnetic flux vector
20
control
40 (initial
40
V/F control
value)
9999
(initial
Control method and control mode selected in Pr.800 (provided that they are selectable with Pr.451)
value)
*1
The control method depends on the motor selected in Pr.71 (Pr.450): Real sensorless vector control for the induction motor, and PM sensorless
vector control for the PM motor.
*2
Operation can start regardless of the setting.
*3
A Vector control compatible option is required.
 Automatic parameter setting by changing the Pr.800 setting
• The Pr.10 and Pr.22 settings are automatically changed when the control method is changed.
• When the control method is changed from V/F control or Advanced magnetic flux vector control to Vector control, the Pr.10
setting is automatically changed as follows.
Pr.
Setting value before change
10
3 Hz (initial value)
• When the control method is changed from Vector control to V/F control or Advanced magnetic flux vector control, the Pr.10
setting is automatically changed as follows.
Pr.
Setting value before change
10
0.5 Hz
• When the control method is changed from V/F control or Advanced magnetic flux vector control to Real sensorless vector
control or Vector control, the Pr.22 setting is automatically changed as follows (only for the ND rating in the FR-E820-
0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or lower, and FR-E820S-0110(2.2K) or lower).
Pr.
Setting value before change
22
150% (initial setting)
• When the control method is changed from Real sensorless vector control or Vector control to V/F control or Advanced
magnetic flux vector control, the Pr.22 setting is automatically changed as follows (only for the ND rating in the FR-E820-
0175(3.7K) or lower, FR-E840-0095(3.7K) or lower, FR-E860-0061(3.7K) or lower, and FR-E820S-0110(2.2K) or lower).
Pr.
Setting value before change
22
200%
98
4. Control Method
4.2 Changing the control method and mode
Control method
Speed control
Torque control
*3
Speed control / torque
control switchover
Speed control
Torque control
Speed control / torque
control switchover
Speed control
Setting value after change
0.5 Hz
Setting value after change
3 Hz (initial value)
Setting value after change
200%
Setting value after change
150% (initial setting)
Condition to start operation
Pr.80 (Pr.453),
Control mode
Pr.81 (Pr.454)
setting
Other than 9999
*2
MC signal
Pr.71
(Pr.450)
Induction
ON: Torque
motor
control OFF:
Speed control
*1
Induction
ON: Torque
motor
control OFF:
Speed control
PM motor
Induction
motor