Mitsubishi Electric FR-E800 Series Instruction Manual page 450

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

16.10
Slip compensation
V/F
V/F
V/F
Under V/F control, the slip of the motor is estimated from the inverter output current to maintain the rotation of the motor
constant.
Pr.
Name
245
Rated slip
G203
246
Slip compensation time
G204
constant
247
Constant output range slip
G205
compensation selection
• Calculate the rated motor slip and set the value in Pr.245 to enable slip compensation.
Slip compensation is not performed when Pr.245 = "0 or 9999".
Synchronized speed at the time of base frequency - rated rotation speed
Rated slip =
NOTE
• When the slip compensation is performed, the output frequency may become larger than the set frequency. Set Pr.1 Maximum
frequency higher than the set frequency.
• Slip compensation will be disabled in the following conditions:
Stall prevention (OLC, OLV) operation, regeneration avoidance operation, auto tuning, stop-on-contact control, acceleration/
deceleration, encoder feedback control operation
Parameters referred to
Pr.1 Maximum
frequencypage 253
Pr.3 Base
frequencypage 428
Initial value
0.01% to
50%
9999
0, 9999
0.5 s
0.01 to 10 s
0
9999
9999
Synchronized speed at the time of base frequency
Setting
range
Set the rated motor slip.
No slip compensation
Set the response time of the slip compensation. Reducing the
value improves the response, but the regenerative overvoltage
(E.OV[]) error is more likely to occur with a larger load inertia.
No slip compensation in the constant power range (frequency
range higher than the frequency set in Pr.3).
Slip compensation is performed in the constant power range.
× 100 [%]
Description
16. (G) Control Parameters
16.10 Slip compensation
11
12
13
14
15
16
17
18
19
20
449

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents