Troubleshooting In Torque Control - Mitsubishi Electric FR-E800 Series Instruction Manual

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

6.7

Troubleshooting in torque control

Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
No.
Condition
Torque control does not
1
operate properly.
When a small torque
command is given, the
2
motor rotates in a
direction opposite to the
start signal.
Torque control cannot
operate normally during
3
acceleration/
deceleration.
The motor vibrates.
Output torque is
4
nonlinear for the torque
command.
Parameters referred to
Pr.72 PWM frequency
selectionpage 184
Pr.178 to Pr.189 (Input terminal function
Pr.800 Control method
selectionpage 97
Pr.807 Speed limit
selectionpage 147
C38 (Pr.932) to C41 (Pr.933) (torque setting voltage (current)
Possible cause
• There is incorrect phase sequence
between the motor wiring and
encoder wiring.
• Pr.800 Control method selection
is not appropriate.
• The speed limit value has not been
input.
• Torque command varies.
• The torque command and the torque
recognized by the inverter are
different.
• Torque offset calibration is
inaccurate.
• Speed limit is operating.
(Speed limit may operate because
the speed limit value will increase or
decrease according to acceleration/
deceleration time setting of Pr.7 and
Pr.8 when Pr.807 = "0".)
• Torque shortage.
selection)page 328
bias/gain)page 323
Countermeasure
• Check the wiring. (Refer to the Instruction Manual
(Connection).)
• Check the Pr.800 setting. (Refer to
• Set the speed limit value. (If speed limit value is not input, it
becomes 0 Hz by default and the motor does not run.)
• Check that the torque command sent from the controller is
correct.
• Set Pr.72 PWM frequency selection lower.
• Set Pr.826 Torque setting filter 1 higher.
• Re-calibrate C38 (Pr.932) Terminal 4 bias command
(torque/magnetic flux), C39 (Pr.932) Terminal 4 bias
(torque/magnetic flux), C40 (Pr.933) Terminal 4 gain
command (torque/magnetic flux), and C41 (Pr.933)
Terminal 4 gain (torque/magnetic flux). (Refer to
323.)
• Re-calibrate C38 (Pr.932) and C39 (Pr.932). (Refer to
323.)
• Set the acceleration/deceleration time shorter.
Alternatively, set "0" for the acceleration/deceleration time.
(Forward/reverse rotation speed limit at this time is the value
at a constant speed.)
• Reset Pr.854 Excitation ratio to the initial value.