Mitsubishi Electric FR-E800 Series Instruction Manual page 266

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

• To prevent the repetitive on/off operation of the signal due to load fluctuation near the detection range, Pr.1492 Load
status detection signal delay time / load reference measurement waiting time can be used to set the delay time. Even
when a fault is detected out of the detection range once, the warning is not output if the characteristics value returns to the
normal range from a fault state within the output delay time.
Load reference
LUP
LDN
E.LDN
LDF warning indication
NOTE
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.41 Up-to-frequency
sensitivitypage 301
Pr.190 to Pr.196 (Output terminal function
Load status
Pr.1492
Pr.1492
ON
ON
selection)page 292
Upper limit fault detection width (Pr.1490)
Upper limit warning detection width (Pr.1488)
Lower limit warning detection width (Pr.1489)
Pr.1492
Lower limit fault detection width (Pr.1491)
Pr.1492
ON
ON
Output shutoff
ON
ON
11. (H) Protective Function Parameters
11.11 Load characteristics fault detection
11
12
13
14
15
16
17
18
19
20
265

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents