Mitsubishi Electric FR-E800 Series Instruction Manual page 389

Compact, high functionality inverters
Hide thumbs Also See for FR-E800 Series:
Table of Contents

Advertisement

• For the terminal used for the SLEEP signal, set "70" (positive logic) or "170" (negative logic) in any parameter from Pr.190
to Pr.196 (Output terminal function selection).
Pr.577 - 1000%
Output frequency
Pr.577 - 1000%
Output frequency
*1
When the PID output shutoff release level is reached during a deceleration stop, output shutoff is released, operation is re-accelerated and PID
control is continued. During deceleration, Pr.576 Output interruption detection level is invalid.
 Integral stop selection when the frequency is limited (Pr.1015)
• The operation for the integral term can be selected when the frequency or the manipulated amount is limited during PID
control.
• The manipulation range can be selected.
Pr.1015 setting
0 (initial value)
1
2
*1
When the frequency reaches the upper limit, or when the PID manipulated amount reaches 100%, the integral stops and the integral term is
retained. When the frequency decreases, the integral does not stop until the manipulated amount reaches -100%, regardless of the output
frequency.
388
15. (A) Application Parameters
15.4 PID control
When Pr.554="0 to 3", reverse operation (Pr.128="10")
Deviation
Pr.576
Less than Pr.575
RUN
PID
SLEEP
When Pr.554="10 to 13", reverse operation (Pr.128="10")
Deviation
Pr.576
Less than Pr.575
RUN
PID
SLEEP
Operation at limited frequency
Integral stop
Integral does not stop.
Integral stop
Pr.575 or more SLEEP period
OFF
ON

Deceleration stop
Pr.575 or more
SLEEP period
OFF
ON
*1
Cancel
level
Time
Cancel
level
Time
Range of manipulation
-100% to +100%
0% to 100%

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents