Tuning the second motor (Pr.463)
• When one inverter switches the operation between two different motors, set the second motor in Pr.450 Second applied
motor, set Pr.463 Second motor auto tuning setting/status = "11", and perform tuning of the second motor.
• Turning ON the RT signal enables the parameter settings for the second motor as shown in the following table.
Function
Motor constant (R1)
Frequency search gain
Auto tuning setting/status
NOTE
• To use the RT signal, set "3" in any parameter from Pr.178 to Pr.189 (Input terminal function selection) to assign the
function to an input terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.9 Electronic thermal O/L
relaypage 238
Pr.65, Pr.67 to Pr.69 Retry
functionpage 250
Pr.71 Applied motor, Pr.450 Second applied
Pr.79 Operation mode
selectionpage 212
Pr.156 Stall prevention operation
selectionpage 256
Pr.178 to Pr.189 (Input terminal function
RT signal ON (second motor)
Pr.458
Pr.560
Pr.463
motorpage 340
selection)page 328
RT signal OFF (first motor)
Pr.90
Pr.298
Pr.96