NOTE
• The slope of frequency rising or lowering by the regeneration avoidance operation will change depending on the regenerative
status.
• The DC bus voltage of the inverter will be approximately
The bus voltage is approx. 311 VDC at an input voltage of 220 VAC (622 VDC at 440 VAC and 813 VDC at 575 VAC).
However, it may vary depending on the input power supply waveform.
• Make sure that the setting value of Pr.883 will not get under DC bus voltage level. The frequency will rise with operation of the
regeneration avoidance function even during operation other than the regenerative operation.
• The stall prevention (overvoltage) (OLV) will be activated only during deceleration, stopping the lowering of output frequency.
On the other hand, the regeneration avoidance function will be activated constantly (Pr.882 = "1") or only at constant speed
(Pr.882 = "2"), and raise the frequency depending on the amount of regeneration.
• When the motor becomes unstable due to the stall prevention (overcurrent) (OLC) during the regeneration avoidance
operation, increase the deceleration time or set a lower value in Pr.883.
 Limiting the regeneration avoidance operation frequency (Pr.885)
• It is possible to assign a limit to the output frequency corrected (rise) by the regeneration avoidance operation.
• Limit of the frequency is output frequency (frequency before regeneration avoidance operation) + Pr.885 Regeneration
avoidance compensation frequency limit value for during acceleration and constant speed. During deceleration, when
the frequency increases due to the regeneration avoidance operation and exceeds the limit value, the limit value will be
retained until the output frequency is reduced to be the half the Pr.885 setting.
• When the frequency that have increased by the regeneration avoidance operation exceeds Pr.1 Maximum frequency, it
will be limited to the maximum frequency.
• When Pr.885 = "9999", the regeneration avoidance compensation frequency limit is disabled.
• Set the frequency around the motor rated slip frequency. Increase the setting value if the overvoltage protection function
(E.OV[]) is activated at the start of deceleration.
Rated motor slip frequency =
Limit level
Pr.885
 Adjusting the regeneration avoidance operation (Pr.665, Pr.886)
• If the frequency becomes unstable during regeneration avoidance operation, decrease the setting of Pr.886 Regeneration
avoidance voltage gain. On the other hand, if an overvoltage fault occurs due to a sudden regeneration, increase the
setting.
• If setting a smaller value in Pr.886 does not suppress the vibration, set a smaller value in Pr.665 Regeneration avoidance
frequency gain.
Synchronized speed at the time of base frequency – rated rotation speed
Synchronized speed at the time of base frequency
Output frequency (Hz)
Pr.885/2
Time
times of the normal input voltage.
2
16.9 Regeneration avoidance function
× Rated motor frequency
447