 Monitor item list (Pr.52, Pr.774 to Pr.776, Pr.992)
• Use Pr.52, Pr.774 to Pr.776, or Pr.992 to select the monitor item to be displayed on the operation panel.
• Refer to the following table to find the setting value for each monitoring. The value in the Pr. setting column is set in each
of the parameters for monitoring (Pr.52, Pr.774 to Pr.776, and Pr.992) to determine the monitor item. The value in the
Communication column is the monitor code for communication. (The items marked with "—" cannot be selected. The circle
(○) in the Negative indication (-) column denotes that the monitored item can be indicated with minus sign during monitoring
via the communication option.
Incremen
Monitor item
t and unit
Output frequency
*16
0.01 Hz
*17
(speed)
Output
0.01 A
*8*9*17
current
Output
0.1 V
*8*17
voltage
Fault indication
Set frequency /
*16
motor speed
0.01 Hz
setting
Operation speed
1 (r/min)
Motor torque
0.1%
Converter output
0.1 V
*8
voltage
Regenerative
0.1%
brake duty
Electronic thermal
O/L relay load
0.1%
factor
Output current
0.01 A
*8
peak value
Converter output
voltage peak
0.1 V
*8
value
Input power
0.01 kW
*9
0.01 kW
Output power
Load meter
0.1%
Motor excitation
0.01 A
*8
current
*10
Position pulse
Cumulative
energization
1h
*6
time
Actual operation
1 h
*6*7
time
Communication
Pr.
Monitor
Monitor
setting
*1
code 1
code 2
1/0/100
H01
40201
2/0/100
H02
40202
3/0/100
H03
40203
0/100
*5
H05
40205
5
*5
H06
40206
6
*5
H07
40207
7
*5
H08
40208
8
*5
H09
40209
9
*5
H0A
40210
10
*5
H0B
40211
11
*5
H0C
40212
12
*5
H0D
40213
13
*5
H0E
40214
14
17
H11
40217
18
H12
40218
19
H13
40219
20
H14
40220
23
H17
40223
Negative
Monitor
indicatio
number
*4
*2
n (-)
*3
1
The inverter output frequency is displayed.
The inverter output current effective value is
2
displayed.
3
The inverter output voltage is displayed.
Each of the last 10 faults is displayed
individually.
5
The set frequency is displayed.
The motor speed is displayed (depending on the
6
Pr.53 setting). (Refer to
The motor torque is displayed as a percentage
7
(0% under V/F control), considering the rated
torque as 100%.
8
The DC bus voltage value is displayed.
Brake duty set in Pr.70 for the regeneration unit
9
set in Pr.30 is displayed.
The motor thermal cumulative value is
A
displayed, considering the thermal operation
level as 100%.
The peak value of output current, which is
B
constantly stored, is displayed. (It is reset with
every startup of the inverter.)
The DC bus voltage peak value, which is
C
constantly stored, is displayed. (It is reset with
every startup of the inverter.)
D
The power at the inverter input side is displayed.
The power at the inverter output side is
E
displayed.
Torque current is displayed as a percentage,
considering Pr.56 setting value as 100%. (0% is
11
displayed under the control mode other than V/
F control.)
12
The motor excitation current is displayed.
The position pulse of the encoder is displayed.
13
(The output voltage is displayed when a vector
control option is not installed.)
The cumulative energization time since the
inverter shipment is displayed. The number of
14
times an integrated value has reached the
maximum value of 65535 hours can be checked
in Pr.563.
The cumulative operation time is displayed. The
number of times an integrated value has
17
reached the maximum value of 65535 hours can
be checked in Pr.564. Use Pr.171 to reset the
cumulative operation time. (Refer to
12. (M) Item and Output Signal for Monitoring
12.2 Monitor item selection on operation panel or via communication
Description
page
268.)
page
277.)