 Selection of set point/measured value input method (Pr.609, Pr.610)
• Select the set point input method by Pr.609 PID set point/deviation input selection and the measured value input
method by Pr.610 PID measured value input selection. Switch the power voltage/current specifications of terminals 2
and 4 by Pr.73 Analog input selection or Pr.267 Terminal 4 input selection to match the specification of the input
device.
• When Pr.133 PID action set point ≠ "9999", Pr.133 is the set point. When the set point is set at Pr.133, the setting
frequency of C2 (Pr.902) is equivalent to 0% and the setting frequency of Pr.125 is equivalent to 100%.
Pr.609, Pr.610 settings
2
3
4
5
*1
When the same input method has been selected for the set point and measured value at Pr.609 and Pr.610, set point input is invalid. (Inverter
runs at set point 0%)
*2
CC-Link, CC-Link IE TSN, CC-Link IE Field Network Basic, and BACnet/IP is available. For the details of each communication, refer to the FR-
A8NC E kit Instruction Manual or the Instruction Manual (Communication).
NOTE
• After changing the Pr.73 or Pr.267 setting, check the voltage/current input selection switch. Incorrect setting may cause a fault,
failure or malfunction. (Refer to
• When terminals 2 and 4 are selected for deviation input, perform bias calibration using C3 (Pr.902) and C6 (Pr.904) to prevent
a minus voltage from being entered as the deviation input signal. Input of a minus voltage might damage devices and the
inverter.
• The following shows the relationship between the input values of the analog input terminals, and the set point and
measured value.
Input
Input terminal
specification
0 to 5 V
Terminal 2
0 to 10 V
0 to 20 mA
0 to 5 V
Terminal 4
0 to 10 V
0 to 20 mA
*3
Can be changed by Pr.73 and Pr.267 and the voltage/current input switch. (Refer to
Input method
*1
Terminal 2
*1
Terminal 4
*2
Communication
PLC function
page 310
for the setting.)
Relationship with analog input
*3
Set point
0 V = 0%
0 V = 0%
5 V = 100%
5 V = 100%
0 V = 0%
0 V = 0%
10 V = 100%
10 V = 100%
0 mA = 0%
0 mA = 0%
20 mA = 100%
20 mA = 100%
0 to 1 V = 0%
0 to 1 V = 0%
5 V = 100%
5 V = 100%
0 to 2 V = 0%
0 to 2 V = 0%
10 V = 100%
10 V = 100%
0 to 4 mA = 0%
0 to 4 mA = 0%
20 mA = 100%
20 mA = 100%
Calibration parameter
Result
Pr.125, C2 to C4 (Pr.902, Pr.903)
Pr.126, C5 to C7 (Pr.904, Pr.905)
page
310.)
15. (A) Application Parameters
15.6 Dancer control
11
12
13
14
15
16
17
18
19
20
399