Earth (ground) fault detection at start

Select whether to make earth (ground) fault detection at start. When enabled, earth (ground) fault detection is performed
immediately after a start signal input to the inverter.
Pr.
249
Earth (ground) fault detection at
H101
start
*1
Gr.1 and Gr.2 are the parameter initial value groups. (Refer to
• If a ground fault is detected at start while Pr.249 = "1", the output-side earth (ground) fault overcurrent (E.GF) is displayed
and the outputs are shut off.
• When the Pr.72 PWM frequency selection setting is high, enable the ground fault detection at start.
NOTE
• Because the detection is performed at start, output is delayed for approx. 20 ms every start.
• Use Pr.249 to enable/disable ground fault detection at operation start.
246
11. (H) Protective Function Parameters
11.3 Earth (ground) fault detection at start
Initial value
Name
Gr.1
0
*1
Setting range
Gr.2
0
1
1
page
52).
Description
Earth (ground) fault detection at start
disabled
Earth (ground) fault detection at start
enabled