UPS System Installation
4.9.3

X-Slot Connections

NOTE
NOTE
For installation and setup of an X-Slot card, contact an Eaton service representative (see page 1-10).
To install wiring to connections:
1.
If not already installed, install the LAN drops.
2.
Unfasten the front door latch and swing the door open (see Figure 4-1).
3.
Remove the right interface entry conduit landing plate to drill or punch holes (see Figure 4-16).
4.
Reinstall the interface entry plate and install the conduit.
5.
Route and install the LAN and other cables to the appropriate X-Slot cards. See Figure 4-21 and
Figure 4-27 for X-Slot communication bay locations.
6.
Close the door and secure the latch.
7 .
Refer to the manual supplied with the X-Slot card for operator instructions.
X-Slot Communication Bay 1
X-Slot Communication Bay 3

Figure 4-27. X-Slot Communication Bays

®
4-34
Eaton
Power Xpert
LAN drops for use with X-Slot cards must be provided by the customer.
When installing external wiring to X-Slot cards, conduit must be installed to the UPS
cabinet. When installing internal wiring to X-Slot terminals, route the wiring through
the internal opening in the X-Slot communication bay.
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
X-Slot Communication Bay 2
X-Slot Communication Bay 4
www.eaton.com/powerquality