1.1.4
Three UPM Plus 1 UPS
The Power Xpert 9395P-900 Plus 1 UPS model (675.900 kVA) contains three sections (see Figure 1-4):
an ISBM or an IOM section rated for a maximum of 900 kVA (to provide future upgradability)
l
a UPM section containing three UPMs. Each UPM is rated for a maximum of 300 kVA for a total maximum
l
of 900 kVA.
an FI-UPM section, which provides N+1 redundancy for the system (see paragraph 1.3.2).
l
FI-UPM
Figure 1-4. Eaton Xpert 9395P-900 Three UPM Plus 1 FI-UPM
NOTE
Startup and operational checks must be performed by an authorized Eaton
Customer Service Engineer, or the warranty terms become void (see Section 1.10).
This service is offered as part of the sales contract for the UPS system. Contact an
Eaton service representative in advance (usually a two-week notice is required) to
reserve a preferred startup date.
®
®
Eaton
Power Xpert
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09