Figure 5-7. Remote Monitor Panel Ii And Relay Interface Module Ii Terminal Locations; Figure 5-8. Remote Monitor Panel Ii, Relay Interface Module Ii, Or Supervisory Contact Module Ii Wiring - Eaton Power Xpert 9395P-900 Series Installation And Operation Manual

High performance ups
Hide thumbs Also See for Power Xpert 9395P-900 Series:
Table of Contents

Advertisement

Installing Options and Accessories
Terminal TB1
Signal Connections
from the UPS

Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations

UPS Can Card J3
Twisted Pair

Figure 5-8. Remote Monitor Panel II, Relay Interface Module II, or Supervisory Contact Module II Wiring

Table 5-5. RMP II, RIM II, or SCM II Wiring Terminations
From
UPS CAN Card
RMP II, RIM II, or SCM II
J3–6 (TX)
J3–7 (TX)
N/A
N/A
N/A
®
5-10
Eaton
Power Xpert
RMP II, RIM II, or SCM II
To
Tightening Torque
Nm (lb in)
TB1–5 (RDX*)
TB1–4 (RDX)
TB3 Line
TB3 Neutral
Ground Terminal
2.7 (24) Maximum
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
0.9 (8)
0.9 (8)
0.9 (8)
0.9 (8)
www.eaton.com/powerquality
Ground
Terminal
Terminal TB3
120 Vac Power
Ground Terminal
Neutral
Line
Remarks
Use twisted pair
120 Vac from
Critical Bus
(Customer
Supplied)

Advertisement