Distributed Bypass Power Wiring Preparation; Inspecting And Unpacking The Ups Cabinets - Eaton Power Xpert 9395P-900 Series Installation And Operation Manual

High performance ups
Hide thumbs Also See for Power Xpert 9395P-900 Series:
Table of Contents

Advertisement

The maximum distance between the REPO and the UPS cannot exceed 150 meters (500 feet).
l
Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac and 28
l
Vdc.
Alarm relay wiring should be a minimum of 22 AWG.
l
3.2.5

Distributed Bypass Power Wiring Preparation

Read and understand the following notes while planning and performing the installation:
All distributed bypass UPS rectifier inputs must come from one source and all bypass input feeds must
l
come from one source.
All UPSs in the distributed bypass system must contain the same number of UPMs. Mixed UPS kVA ratings
l
are not permitted.
Distributed bypass UPS input wiring size requirements and output wiring size requirements from the UPSs
l
to the tie cabinet or distribution panel are the same as listed in Table 3-7 to Table 3-10.
The 9395P 480V unit is designed for operation on a ground wire source of supply. There is no additional
l
connection point for a neutral conductor. The output of this UPS will not directly support phase to neutral
loads.
MOBs with dual auxiliary contacts are to be provided by the customer. Table 3-26 lists the recommended
l
rating for the MOBs.
The tie cabinet is provided by the customer and must contain Module Output Breakers (MOBs) with dual
auxiliary contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed to go to bypass
individually during servicing. All UPMs will go to bypass instead of just the UPM needing service, decreasing
critical load protection. With dual auxiliary MOBs, one UPM can be bypassed while the remaining UPMs
support the load as long as the remaining UPMs have the capacity to do so.
3.3

Inspecting and Unpacking the UPS Cabinets

The UPS cabinet is divided into two sections palleted separately for shipping. The sections are shipped bolted
to wooden pallets (see Figure 3-18 and Figure 3-19) and protected with outer protective packaging material.
The UPS sections are heavy (see Table 3-1). If unpacking and unloading instructions are not closely
followed, the cabinets may tip and cause serious injury.
Eaton
NOTE
On all 9395P models that will be fed by a site generator at any time it is
recommended to have an "On Generator" sensing input connected and proven
functional. This allows the UPS to optimize its operation with the generator. This
function includes reduced input current and battery current limits, slower walk-in to
ease the load step on the generator initially, and HIGH ALERT mode for ESS and
VMMS operation.
HIGH ALERT mode is desired because any loads with a leading power factor will
not be seen by the generator. Rectifier operation will be much softer while on
generator thereby increasing overall system stability.
NOTE
For full-rated operation of a Distributed Bypass System when in Bypass or ESS
mode, the line frequency impedance of all conduction paths must be equal when
assessed from the point where the Bypass Power Source connects to the System
Switchgear to the point where the Common Load connects to the System
Switchgear.
®
®
Power Xpert
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
UPS Installation Plan and Unpacking
WARNING
www.eaton.com/powerquality
3-39

Advertisement

Table of Contents
loading

Table of Contents