UPM Air Filters

Figure 9-2. UPM Section Air Filter Locations

3.
If the UPS configuration included an FI-UPM model, check the FI-UPM air filter (located behind the front
panel) and wash or replace as necessary. See Figure 9-3 for the filter location. The FI-UPM filter size is 20"
X 44" X 0.25" . Contact an Eaton service representative for a replacement filter. To remove the filter:
a.
Remove one top screw and two bottom screws securing the FI-UPM front panel (refer to the Eaton
®
Power Xpert
9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)). Lift the
panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b.
Pull the foam filter over the screw heads on the cabinet mounted studs and remove the filter from the
cabinet.
Verify washed filter is thoroughly dry before reinstalling.
Vérifier que les filtres sont bien secs avant de les réinstaller.
c.
Push the washed or new foam filter over the screw heads on the cabinet mounted studs until seated
against the cabinet.
d.
Reinstall the FI-UPM front panel removed in Step a and secure with the retained hardware.
®
®