Installation Considerations - Eaton Power Xpert 9395P-900 Series Installation And Operation Manual

High performance ups
Hide thumbs Also See for Power Xpert 9395P-900 Series:
Table of Contents

Advertisement

UPS Installation Plan and Unpacking
The other aspect is the rate of change of temperature and/or RH, which can occur during transitions within
l
the cooling system. Examples: changing the mixture ratio of inside versus outside air, or external changes in
the outside air when going from nighttime into day, and back to night.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the
environment created by this microclimate exceeds the Eaton 9395P UPS operating specification, the UPS
reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns
for any servers that are exposed to them.
Do not expose the UPS for overly aggressive environments, such as salt mist or corrosive gases. High relative
humidity accelerates the effects of contaminants. The UPS should be installed in a G1 environment (based on
ANSI/ISA S-71.04 classifications). If the UPS is used in a more aggressive environment, it can cause reduced
product life and possibly early failure. If the installation location does not meet the recommended environment,
contact Eaton service representative for further information.
3.2.2

Installation Considerations

The UPS system installation must meet the following guidelines:
The system must be installed on a level floor suitable for computer or electronic equipment.
l
The system must be installed in a temperature and humidity controlled indoor area free of conductive
l
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the maximum weight requirements shown in Table 3-1
and the size requirements shown in Figure 3-1 through Figure 3-17. Dimensions are in millimeters (inches).
Table 3-1 does not include the weight of the Field Installed UPM (FI-UPM). For FI-UPM weights and
dimensions, refer to the Eaton
(P-164000503), listed in paragraph 1.8.
Table 3-1 includes the weights of the heaviest cabinet configuration. Actual weights may be less due to the
installed configuration. Weights are in kilograms (pounds).
®
3-2
Eaton
Power Xpert
Power Xpert
®
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
R 9395P UPS Field Installed UPM Mechanical Installation Manual
®
www.eaton.com/powerquality