Installing Options and Accessories
Bypass Not Available
Shutdown Imminent
Figure 5-11. Supervisory Contact Module II TB2
NOTE
NOTE
®
5-14
Eaton
Power Xpert
System Normal
No Redundancy
On Generator
On Battery
UPS Alarm
On Bypass
Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
Supervisory contacts require an external power supply. Internal 24 Vdc is not
capable of supplying contact current.
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09