Figure 6-17. Simplified Dual-Feed Ups With Maintenance Bypass Panel - Eaton Power Xpert 9395P-900 Series Installation And Operation Manual

High performance ups
Hide thumbs Also See for Power Xpert 9395P-900 Series:
Table of Contents

Advertisement

Understanding UPS Operation
RIB:
Rectifier Input Breaker
BIB:
Bypass Input Breaker
MIS:
Maintenance Isolation Breaker
MBP:
Maintenance Bypass Breaker
NOTE If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a single feed with two
upstream feeder breakers, must be provided: one for the UPS or rectifier input breaker (RIB) (if installed) and one for the maintenance bypass
input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass input
breaker (BIB) is installed in the maintenance bypass and a single-feed UPS is being installed, a single feed to the maintenance bypass is
acceptable for supplying both the UPS and the bypass.

Figure 6-17. Simplified Dual-Feed UPS with Maintenance Bypass Panel

®
6-22
Eaton
Power Xpert
To UPS
To UPS
Rectifier
Bypass
Input
Input
RIB
BIB
Output
from
UPS
Static
Switch
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
AC Input
AC Input
MBP
MIS
MAINTENANCE
BYPASS PANEL
(Supplied by Others)
Backfeed
Contactor
K5
Output
K3
Contactor
UPS
Battery
Breaker
BATTERY SYSTEM
CRITICAL LOAD
DISTRIBUTION UNIT
www.eaton.com/powerquality

Advertisement

Table of Contents
loading

Table of Contents