Figure 5-2. Hot Sync CAN Bridge Card Connections

Table 5-1. Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
Name
1
Alarm
2
Alarm Return
3
Alarm Relay NC
4
Alarm Relay Com
5
Alarm Relay NO
6
TX
7
TX
8
CAN L
9
Can H
10
Shield
®
®
Eaton
Power Xpert
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status
Alarm
Description
Programmable UPS alarm. Activated by a remote dry contact closure.
Alarm Relay NC Normally-closed contact opens when UPS is on bypass.
Bypass contact return.
Normally-open contact closes when UPS is on bypass.
RMP II, RIM II, and SCM II connections.
CAN input for parallel operation.