The VMMS feature has three configurable modes of operation: Online mode, Online mode with VMMS, and
High Alert mode. All modes are selectable from the front panel.
VMMS mode supports both distributed bypass and SBM parallel configurations.
In High Alert mode, all idle UPMs go online for one hour. At the completion of the hour, the UPS defaults back
to VMMS mode. If the high alert command is received during the one hour, the one hour timer will be restarted.

1.3.11 Monitoring and Communication

The UPS system can be further enhanced by adding optional accessories such as a Remote Emergency
Power-off (REPO) control, RMP II, SCM II, RIM II, or X-Slot communication cards. See Chapter 5, "Installing
Options and Accessories" for additional information.
Remote Monitor Panel II (RMP II)
l
allowing monitoring of the operational status and alarm condition of the UPS from virtually any location
within the facility.
Relay Interface Module II (RIM II)
l
operating status and alarm condition.
Supervisory Contact Module II (SCM II)
l
system equipment and the customer's monitor.
X-Slot Cards
l
Modbus.
PredictPulse
l
management service from Eaton that collects and analyzes data from connected power infrastructure
devices, providing us with the insight needed to make recommendations and take action on your behalf. It's
also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of
eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of alarms and system
performance (load, temperature/humidity, battery health, energy savings and service level) to reduce
downtime risk and expedite repairs. PredictPulse also shares real-time status and trend information via an
online dashboard and smartphone mobile app (Apple and Android), giving subscribers insights about past
and current performance, a list of all active alarms, and asset management data (i.e., battery date codes, last
and next scheduled service dates, firmware versions). The service notifies customers of critical alarms,
supports remote diagnostics, and facilitates smart dispatch of technicians. PredictPulse requires a Power
Xpert® Gateway Card (PXGX) connectivity card in an X-Slot communication bay and an Environmental
Monitoring Probe (EMP) for battery temperature/humidity monitoring.
See Chapter 8, "Communication" for additional information on monitoring and communication features.
1.4

Battery System

Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead-acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPSs in distributed bypass and parallel systems must use a separate battery system.
Consult the Eaton
Installation Manual (P-164000580) for specifics on battery cabinet usage with the Power Xpert 9395P models.
Eaton
– Optional X-Slot cards support several protocols, such as SNMP , HTTP , IBM AS/400, and
Remote Monitoring and Management Service
®
®
Power Xpert
9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR)
®
®
Power Xpert
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
– An optional RMP II contains backlit status indicators and a local horn,
– An optional RIM II uses relay contact closures to indicate the UPS
– An optional SCM II establishes an interface between the UPS
– PredictPulse is a subscription monitoring and