Installing Options and Accessories
5.1

Installing an Optional Hot Sync CAN Bridge Card

As an option, a Hot Sync Controller Area Network (CAN) Bridge Card, shown in Figure 5-1, can be installed to
provide connectivity for operational mode control of a parallel system. In addition, this card can be used to
connect optional system monitoring devices, such as a Remote Monitor Panel II, a Relay Interface Module II,
or a Supervisory Contact Module II to the UPS.

Figure 5-1. Hot Sync CAN Bridge Card

NOTE
To install the card:
1.
Verify the UPS system is turned off and all power sources are removed. See Chapter 7, "UPS Operating
Instructions" for shutdown instructions.
2.
Unfasten the front door latch and swing the door open (see Figure 4-1).
3.
Install the Hot Sync CAN Bridge Card into an open X-Slot communication bay on the front of the UPS. See
Figure 4-21 and Figure 4-27 for X-Slot communication bay locations.
To locate the appropriate terminals on the Hot Sync CAN Bridge Card, see Figure 5-2 and Table 5-1.
®
5-2
Eaton
Power Xpert
Only one Hot Sync CAN Bridge Card can be installed in the UPS. Multiple CAN
cards are not supported and will cause system conflicts.
®
9395P-900 UPS Installation and Operation Manual P-164000501—Rev 09
Plug-in Terminal