Commissioning
6.5 Resetting the safety functions to the factory setting
6. Go offline.
7. Switch off the inverter power supply.
8. Wait until all LEDs on the inverter are dark.
9. Switch the inverter power supply on again.
You have restored the safety functions in the inverter to the factory settings.
Exception: The password for the safety functions is not reset.
Procedure with an operator panel
1. Set p0010 = 30
Activate reset settings.
2. p9761 = ...
Enter the password for the safety functions
3. Start the reset with p0970 = 5.
4. Wait until the inverter sets p0970 = 0.
5. Set p0971 = 1.
6. Wait until the inverter sets p0971 = 0.
7. Switch off the inverter power supply.
8. Wait until all LEDs on the inverter are dark.
9. Switch on the inverter power supply again.
You have restored the safety function settings of your inverter to the factory settings.
Restoring the inverter to the factory setting
Procedure with STARTER
1. Go online
2. Select the button
You have reset the inverter to the factory settings.
Procedure with operator panel
1. Select the "Extras" menu
2. Select the "Parameter settings" menu
3. Select the entry "Restore drive to factory settings"
You have reset the inverter to the factory settings.
78
Safety functions password (Page 120)
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
SIMATIC ET 200pro FC-2 converter