Advanced commissioning
7.20 Switchover between different settings
Figure 7-44
You can use parameter p0180 to define the number of drive data sets (1 or 2).
Table 7- 36
Parameter
p0010 = 15
p0180
p0010 = 0
Table 7- 37
Parameter
p0820
p0826
r0051
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the Parameter Manual.
Note
You can only switch over the motor data of the drive data sets in the "ready for operation"
state with the motor switched-off. The switchover time is approx. 50 ms.
If you do not switch over the motor data together with the drive data sets (i.e. same motor
number in p0826), then the drive data sets can also be switched over in operation.
190
Switching over between different settings using drive data sets (DDS)
Selecting the number of drive data sets
Description
Drive commissioning: Data sets
Drive data sets (DDS) number(factory setting: 1)
Drive commissioning: Ready
Parameters for switching the drive data sets:
Description
Drive data set selection DDS
Motor changeover, motor number
Displaying the number of the DDS that is currently effective
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF