  • Page 2 ___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring ET 200SP Digital output module ___________________ DQ 8x24VDC/0.5A HF Parameters/address space (6ES7132-6BF00-0CA0) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 12/2017 A5E03576680-AE...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6: Table Of Contents

    Table of contents Preface ..............................3 Documentation guide ..........................6 Product overview ..........................11 Properties ..........................11 Wiring ..............................14 Wiring and block diagram ....................... 14 Parameters/address space ........................17 Parameters ..........................17 Explanation of parameters ...................... 19 Address space ........................20 Interrupts/diagnostics alarms .........................
  • Page 7: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 8 You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/73021864). Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).
  • Page 9 ● Manuals, characteristics, operating manuals, certificates ● Product master data You can find "mySupport" - CAx Data in the Internet (http://support.industry.siemens.com/my/ww/en/CAxOnline). Application examples The application examples support you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.
  • Page 10 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA With SIEMENS PRONETA (PROFINET network analysis), you analyze the plant network during commissioning. PRONETA features two core functions: ● The topology overview independently scans PROFINET and all connected components.
  • Page 11 Documentation guide SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 12: Product Overview

    Product overview Properties Article number 6ES7132-6BF00-0CA0 (Number in pack: 1 unit) 6ES7132-6BF00-2CA0 (Number in pack: 10 units) View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③ ⑨ 2D matrix code Function and firmware version ④...
  • Page 13 Product overview 2.1 Properties Properties The module has the following technical properties: ● Digital output module with 8 outputs ● Source output (PNP, P-switching) ● Supply voltage L+ ● Output current 0.5 A (per channel) ● Configurable diagnostics (per channel) ●...
  • Page 14 ● Shield connector See also You can find additional information on the accessories in the system manual Distributed I/O System ET 200SP. See also ET 200SP distributed I/O system (https://support.industry.siemens.com/cs/ww/en/view/58649293) Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 15: Wiring

    You can use and combine the different wiring options for all channels. You can find information on wiring the BaseUnit in the system manual Distributed I/O System ET 200SP (http://support.automation.siemens.com/WW/view/en/58649293). Note • The load group of the module must begin with a light-colored BaseUnit. Keep this in mind also during the configuration.
  • Page 16 Wiring 3.1 Wiring and block diagram Wiring: 1 and 2-wire connection of actuators The following figure shows an example of the terminal assignment of the digital output module DQ 8×24VDC/0.5A HF on the BaseUnit BU type A0 without AUX terminals (1- and 2-wire connection).
  • Page 17 Wiring 3.1 Wiring and block diagram Power LED (green) Figure 3-1 Block diagram and terminal assignment for 1- and 2-wire connection of actuators Wiring: 3-wire connection of actuators The following figure shows an example of the terminal assignment of the digital output module DQ 8×24VDC/0.5A HF on the BaseUnit BU type A0 with AUX terminals (3-wire connection).
  • Page 18: Parameters/Address Space

    Parameters/address space Parameters Parameters of the DQ 8x24VDC/0.5A HF Specify the module properties with the various parameters in the course of your STEP 7 configuration. The following table lists the configurable parameters. The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible: ●...
  • Page 19 Parameters/address space 4.1 Parameters Parameter Value range Default Configuration Scope with configuration software, in RUN e.g., STEP 7 (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Reaction to CPU STOP • Turn off Channel Module Turn off Keep last value •...
  • Page 20: Explanation Of Parameters

    A potential group ends with the dark-colored BaseUnit, which follows a light-colored BaseUnit or server module in the station configuration. See also See system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 21: Address Space

    Parameters/address space 4.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image output/input. Configuration options of DQ 8x24VDC/0.5A HF You can configure the module with STEP 7 (TIA Portal) or with a GSD file. If you configure the module by means of a GSD file, the configurations are available under various short designations/module names;...
  • Page 22 Parameters/address space 4.3 Address space Note The following functions are only fully available when the submodule X.1 is configured and the IO controller to which submodule X.1 is assigned has established a connection to the IO device. • Firmware update •...
  • Page 23 Parameters/address space 4.3 Address space Address space for configuration as 1 x 8-channel DQ 8x24VDC/0.5A HF, QI The following figure shows the assignment of the address space for the configuration as 1 x 8-channel module with value status. You can freely assign the start address for the module.
  • Page 24 Parameters/address space 4.3 Address space The following figure shows the assignment of the address space for submodules 1, 2, 3, and 4 and the value status. Figure 4-3 Address space for configuration as 1 x 8-channel DQ 8x24VDC/0.5A HF MSO with value status Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 25 Parameters/address space 4.3 Address space Address space for configuration as 2 x 4-channel DQ 8x24VDC/0.5A HF V2.0, S.2 The figure below shows the address space assignment for configuration as a 2 x 4-channel module without value status. Each of the two submodules has a freely assignable start address. Figure 4-4 Address space for configuration as 2 x 4-channel DQ 8x24VDC/0.5A HF V2.0, S.2 without value status...
  • Page 26 Parameters/address space 4.3 Address space Address space for configuration as 4 x 2-channel DQ 8x24VDC/0.5A HF V2.0, S.4 The figure below shows the address space assignment for configuration as a 4 x 2-channel module without value status. Each of the four submodules has a freely assignable start address. Figure 4-6 Address space for configuration as 4 x 2-channel DQ 8x24VDC/0.5A HF V2.0, S.4 without value status...
  • Page 27 Parameters/address space 4.3 Address space Address space for configuration as 4 x 2-channel DQ 8x24VDC/0.5A HF V2.0, S.4 QI The figure below shows the address space assignment for configuration as a 4 x 2-channel module with value status. Each of the four submodules has a freely assignable start address. Figure 4-7 Address space for configuration as 4 x 2-channel DQ 8x24VDC/0.5A HF V2.0, S.4 QI with value status...
  • Page 28: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error displays LED displays The figure below shows the LED displays (status and error displays) of the DQ 8x24VDC/0.5A HF: ① DIAG (green/red) ② Channel status (green) ③ Channel error (red) ④ PWR (green) Figure 5-1 LED displays Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 29 Interrupts/diagnostics alarms 5.1 Status and error displays Meaning of the LEDs The tables below explain the meaning of the status and error displays. Corrective measures for diagnostics alarms can be found in section Diagnostics alarms (Page 30). DIAG LED Table 5- 1 Error display of the DIAG LED DIAG LED Meaning...
  • Page 30: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The DQ 8×24VDC/0.5A HF digital output module supports diagnostics interrupts. Diagnostics interrupts The module generates a diagnostic interrupt at the following events: ● Short-circuit ● Wire break ● Parameter assignment error ● Supply voltage missing ●...
  • Page 31: Diagnostics Alarms

    Interrupts/diagnostics alarms 5.3 Diagnostics alarms Diagnostics alarms Diagnostics alarms A diagnostics alarm is generated and the DIAG-LED flashes on the module for each diagnostics event. You can read out the diagnostics alarms, for example, in the diagnostics buffer of the CPU. You can evaluate the error codes with the user program. Note Parallel connection of two outputs For parallel connection of two outputs for redundant control of a load, the channel...
  • Page 32: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DQ 8x24VDC/0.5A HF Article number 6ES7132-6BF00-0CA0 General information Product type designation DQ 8x24 V DC/0.5 A HF Firmware version V2.0 FW update possible • usable BaseUnits BU type A0 Color code for module-specific color identifica- CC02 tion plate Product function...
  • Page 33 Technical specifications 6.1 Technical specifications Article number 6ES7132-6BF00-0CA0 Supply voltage Rated value (DC) 24 V permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Output voltage Rated value (DC) 24 V Power loss Power loss, typ.
  • Page 34 Technical specifications 6.1 Technical specifications Article number 6ES7132-6BF00-0CA0 Switching frequency 100 Hz with resistive load, max. • 2 Hz with inductive load, max. • 10 Hz on lamp load, max. • Total current of the outputs 0.5 A Current per channel, max. •...
  • Page 35 This residual current does not depend on the setting for the Diagnostics: Wire break parameter. Dimension drawing See manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 36: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
  • Page 37 Parameter data record A.1 Parameter assignment and structure of parameter data record Data record structure Figure A-1 Structure of data record 128 or data records 64 to 71 Header information The figure below shows the structure of the header information. Figure A-2 Header information Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0)
  • Page 38 Parameter data record A.1 Parameter assignment and structure of parameter data record Parameter The figure below shows the structure of the parameters for channels 0 to 7. You enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure of byte x to x+2 for channels 0 to 7 Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Manual, 12/2017, A5E03576680-AE...
  • Page 39 Parameter data record A.1 Parameter assignment and structure of parameter data record Error transmitting the data record The module always checks all values of the data record to be sent. The module applies the values from the data record only when all values have been transmitted without errors. The WRREC instruction for writing data records returns the appropriate error code if there are errors in the STATUS parameter.