Parameter Description
p0344
p0604
p0605
p0612
p0627
p0625
r0632
p0640
Further information is provided in the function charts 8016 and 8017 of the List Manual.
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Motor weight (for thermal motor type) (factory setting: 0.0 kg)
Mot_temp_mod 2/KTY alarm threshold (factory setting: 130.0°
C)
Motor temperature > p0604 ⇒ fault F07011.
Mot_temp_mod 1/2 threshold (factory setting: 145.0° C)
Motor temperature > p0605 ⇒ alarm A07012.
Mot_temp_mod activation
.01
1 signal: Activate motor temperature model 2 for induc-
tion motors
.09
1 signal: Activate motor temperature model 2 expan-
sions
The inverter sets bit 09 = 1 after commissioning. If you
load the parameter settings for firmware version ≤ V4.6
into the inverter, bit 09 = 0 remains.
Motor overtemperature, stator winding (factory setting: 80 K)
Motor ambient temperature during commissioning (factory setting: 20° C)
Specification of the motor ambient temperature in °C at the instant of the motor data
identification.
Mot_temp_mod stator winding temperature [°C]
Current limit [A]
7.16 Motor protection by calculating the temperature
Advanced commissioning
After selecting an induc-
tion motor (p0300) or a
listed induction motor
(p0301) during the com-
missioning, the inverter
sets the parameters to
values appropriate for
the motor.
The parameters are
write-protected for listed
motors (p0301 ≥ 0).