Siemens SIMATIC ET 200pro FC-2 Operating Instructions Manual page 135

Low voltage converter for the distributed i/o system
Hide thumbs Also See for SIMATIC ET 200pro FC-2:
Table of Contents

Advertisement

Figure 7-17
Example
Setting with the motorized potentiometer as setpoint source:
Parameter
p1070 = 1050
Parameter
Table 7- 15
Basic setup of motorized potentiometer
Parameter
Description
p1035[0...n]
BI: Motorized potentiometer
setpoint higher
p1036[0...n]
BI: Motorized potentiometer
setpoint lower
p1040[0...n]
Motorized potentiometer
start value [rpm]
p1047
MOP ramp-up time [s]
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Function chart of the motorized potentiometer
Description
Interconnects the main setpoint with the motorized potentiometer output.
Setting
Signal source to continuously increase the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.13
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
Signal source to continuously decrease the setpoint
The factory setting depends on the inverter.
Inverters with PROFIBUS or PROFINET interface:
[0] 2090.14
[1] 0
Inverters without PROFIBUS or PROFINET interface: 0
Start value that is effective when the motor is switched on.
Factory setting: 0 rpm
MOP ramp-up time
Factory setting: 10 s
Advanced commissioning
7.8 Setpoints
133