Note
Values in italics
Values in italics in the following tables mean that you have to adjust these values for a
specific request.
Reading parameter values
Table 7- 4
Request to read parameters
Data block
Header
Address, parameter 1
Address, parameter 2
...
Address, parameter m
Table 7- 5
Inverter response to a read request
Data block
Header
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Byte n
Reference
00 hex ... FF hex
01 hex (ID of drive objects, at G120 al-
ways = 1)
Attribute
10 hex:
Parameter value
20 hex:
Parameter description
0001 hex ... FFFF hex
Parameter number
0000 hex ... FFFF hex
Number of the 1st index
(for parameters without index: 0000 hex)
...
...
...
...
Byte n
Reference (identical to a read request)
01 hex (ID of drive objects, at G120 al-
ways = 1)
7.4 Drive control via PROFIBUS and PROFINET
Bytes n + 1
01 hex: Read job
Number of parameters (m)
Number of the indices
00 hex ... EA hex
(For parameters without index: 00 hex)
Bytes n + 1
01 hex: Inverter has executed the read re-
quest.
81 hex: Inverter was not able to completely
execute the read request.
Number of parameters (m)
(identical to the read request)
Advanced commissioning
103
n
0
2
4
6
8
...
...
...
...
n
0
2