Appendix
A.2 The device trace in STARTER
Figure A-3
In the example, the trace starts if digital inputs DI 0 and DI 3 are high, and DI 2 is low. The
state of the other digital inputs is not relevant for the trigger condition.
Further, you can either set an alarm or fault as start condition.
Display options
In this area, you can set how the measurement results are displayed.
● Repeat measurement
This places the measurements that you wish to perform at different times above one
other.
● Arrange curves in tracks
This defines whether the device trace will show all measured values on a common zero
line or on separate zero lines.
● Measuring cursor On
This allows you to analyze the measuring intervals in more detail.
Save to device (memory card)
In this area, you define whether the device trace will save successive measurements in
directory /USER/SINAMICS/DATA/TRACE on a inserted memory card.
Displaying the measurements backed up on the memory card
Procedure
1. Insert the memory card into a card reader.
2. Go to the "Measurements" tab in the device trace.
3. Open the read out ACX files with the "Open measurements" button.
264
Selecting bits for the trace trigger:
Upper row hex format
Lower row binary format
Define the bits for the trace trigger:
Upper row hex format
Lower row binary format
Trigger as bit pattern of r0722 (status of the digital inputs)
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
SIMATIC ET 200pro FC-2 converter