Technical data
11.5 Electromagnetic compatibility of the converters
Limit values for compliance with EN 61800-3 Category C3
The following table lists the key limit values for compliance with EN 61800-3 on devices with
restricted availability for a drive system in accordance with Category C3 (Category C3: Drive
system (PDS) with a rated voltage of < 1000 V. For use in a second environment), i.e., use
in second environment (industrial) with commissioning and installation carried out by an
EMC expert.
Table 11- 6
EMC phenomena
Radiated emissions
Conducted emissions
Table 11- 7
Limit values for interference immunity for a drive system compliant with Category C3
EMC phenomena
Voltage dips
Voltage interruptions
Harmonics at rated load
Electrostatic discharge
Interference pulses
High-frequency electromagnetic field, ampli-
tude-modulated
Ground leakage current
1) Reduction of motor speed
2) Shutdown on fault F00003 "Undervoltage"
3) Shutdown on fault F00002 "Overvoltage"
The requirements of the product standard for a drive system, according to C3, are fulfilled.
252
Limit values for noise radiation for a drive system compliant with Category C3
Basic standard
for test proce-
dures
EN 61800-3-A11
EN 61800-3-A11
Motor operation
EN 61800-3-A11
Regenerative
EN 61800-3-A11
feedback
EN 61000-4-2
Burst
EN 61000-4-4
Voltage surge
EN 61000-4-5
EN 61000-4-3
EN 61800-5-1
Basic standard
Limit value
for test proce-
dures
EN 55011
Class A, Group 1
EN 55011
Class A, Group 2
Level
30 %, 10 ms 1)
60 %, 100 ms 1)
95 %, 5 s 2)
100 %, 230 ms 2)
100 %, 120 ms (regenerative feed-
back) 3)
5.
7.
18,4%
15,6%
20,3%
18,4%
8 kV, air discharge (housing)
2 kV/5 kHz (electric power cable)
2 kV, phase – ground (electric power
cable)
1 kV, phase – phase (electric power
cable)
80 MHz – 1000 MHz, 10 V/m,
80 % AM
See the two tables below.
Operating Instructions, 04/2018, FW V4.7 SP10, A5E34257324B AF
Evaluation crite-
rion
11.
13.
8,8%
8,4%
9,8%
9,3%
SIMATIC ET 200pro FC-2 converter
B
C
C
C
C
--
B
B
B
B
A
--