3. Rack Installation
Power Distribution Unit Installation
Power Distribution Unit Installation
This section describes how to install a power distribution unit in a rack.
Installing Power Distribution Unit (1U)
This section describes how to install a 1U power distribution unit in a rack.
1
Attach the M6 cage nuts to the rear rack pillar.
Attachment positions
•
On either side, insert four M6 cage nuts in the 1st and 3rd holes above the power distribution unit base
line.
M6 cage nut
3rd hole
1st hole
•
Attachment procedure
Clip the M6 cage nut tabs into the desired hole from the inside.
Side view
2
Attach the cable holders to the power distribution unit.
Use four M3 screws to attach the cable holders.
• Do not connect any devices other than the ETERNUS DX to the power distribution
unit.
(Rack pillar: rear)
[Left]
1U
Power distribution unit
Power distribution unit
base line
M6 cage nut
Rack pillar (square hole)
[Right]
M6 cage nut
3rd hole
1st hole