Eda2530E Standard Configuration For Cwa Parent And Stand Alone Shelf - Ericsson EDA 2530 Commissioning Instructions

Commissioning procedure for cable and wireless access
Table of Contents

Advertisement

2.4.2
EDA2530E Standard Configuration for CWA Parent and Stand Alone
Shelf
This sub-section describes the standard configuration for CWA EDA2530 DLE
(EDAxx01) Parent and Stand Alone shelves only. The site engineer must refer to
the site specific configuration information for the site being commissioned.
This standard configuration allows for additional units to be provided at a later date
with minimal changes to the existing configuration.
The 64 x ADSL2+ units are inserted in even numbered slots from slot 2 up to slot 18
in increasing order towards the right.
The 64 x POTS/VoIP units are inserted in odd numbered slots from slot 3 up to slot
19 in increasing order towards the right.
Note that each 64 x ADSL and 64 x POTS unit has it's relevant 64 x COMBI
Interface + I/O POTS + TAM Connection Unit (02HAT 00282 AAQ) fitted above the
pair of units. (A protection unit does not require an associated Connection Unit.)
Each 32 x SHDSL unit has one 32 x TAM Connection Unit (02HAT00136AAR) fitted
directly above the unit.
The 32 x SHDSL units are inserted in slots 20 and 21 and then in slots 18 and 19 if
more than two SHDSL units are required.
Figure 2.4 – EDA 2530 Example Configuration for CWA Shelf
1/153 22-FGC 101 0239/2 Uen Rev J 2010-04-01
EDA 2530 Commissioning Procedure for Cable and Wireless Access
© Ericsson AB 2010
Commercial in confidence
16 (200)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents