b.
c.
d.
8.2.3

FAN Unit Extraction/Insertion

WARNING: This test should be completed quickly, as the equipment should only
operate without a fan unit for less than 5 minutes.
a.
b.
1/153 22-FGC 101 0239/2 Uen Rev J 2010-04-01
Check the "cpPowerProblemTrap" alarm appears on the alarm browser.
st
Switch ON the 1
and 2
cabinet. This will reconnect power to Socket Vb1 on the Power Supply
Connection Unit in slot 22.
Check the Green Vb1 PWR LED is lit on the Power Supply Connection Unit
in slot 22.
Check the "cpPowerProblemTrap" alarm clears on the alarm browser.
rd
Switch OFF the 3
cabinet. This will disconnect the power supply from Socket Vb2 on the
Power Supply Connection Unit in slot 22.
Check the Green Vb2 PWR LED is extinguished on the Power Supply
Connection Unit in slot 22.
Check the "cpPowerProblemTrap" alarm appears on the alarm browser.
rd
Switch ON the 3
and 4
cabinet. This will reconnect power to Socket Vb2 on the Power Supply
Connection Unit in slot 22.
Check the Green Vb2 PWR LED is lit on the Power Supply Connection Unit
in slot 22.
Check the "cpPowerProblemTrap" alarm clears on the alarm browser.
Extract the fan tray unit present in the subrack central part and check that:-
To remove the fans assembly unscrew the two fixing screws and pull the
fans assembly.
Check the following alarms appear on the alarm browser:-
"cpHighTemperatureTrap"
"cpEqtSubrackCoolingFanStatusChangedTrap"
"cpCoolingFanFailureTrap"
Reinsert the FAN tray unit.
To replace the fans assembly, position the fans assembly in the subrack so
that the two gudgeon pins located in the subrack fit into their respective
holes in the fans assembly. Push the assembly and then screw in the two
fixing screws.
EDA 2530 Commissioning Procedure for Cable and Wireless Access
nd
Circuit Breakers at the top of the EDA 2530
th
and 4
Circuit Breakers at the top of the EDA 2530
th
Circuit Breakers at the top of the EDA 2530