T10 Analogue Output 2 Mode; Calibrate T5/6 Analogue Input 1 Full Scale; T5/6 Analogue Input 1 Sample Time - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
7.24

T10 analogue output 2 mode

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
The following modes are available for the analogue outputs.
Parameter value
Parameter string
0
1
2
3
In voltage mode the output range is -10V to 10V. If the scaling parameter is 1.000 then -10V and 10V are produced when the source parameter is at -
maximum and maximum respectively. Different scaling can be applied with Pr 7.23. If the result of the scaling produces an output of more than +/-
100% the output is clamped within the +/-10V range.
In current modes with a scaling parameter of 1.000 the minimum and maximum current are produced when the source parameter is at 0 and
maximum respectively. Therefore in 4 - 20mA mode the output is 4mA when the source parameter is zero. Different scaling can be applied with
Pr 7.23. If the result of the scaling produces an output of more than 100% the output is clamped at 20mA
If high speed update mode is selected and the source for the output is one of the parameters designated for high speed analogue output operation
(see start of this section) the output is updated at a higher rate with special scaling. If the parameter selected is not designated for this mode the
output is updated at the normal rate. If speed feedback or power is selected for high speed mode for both analogue output 1 and analogue output 2
the setting is ignored for analogue output 2. If the high speed mode is selected the output is always a voltage signal.
7.25

Calibrate T5/6 analogue input 1 full scale

Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
Background
Setting this bit will cause the drive to re-calibrate the full scale level of analogue input 1 provided the input voltage is below +1.5V or above +2.5V. This
parameter is cleared by the software automatically when the calibration is complete. If the input voltage is above +2.5V the input voltage itself is used
for calibration, and so after calibration this level will be full scale for the input. If the input voltage is below +1.5V the internal reference is used for
calibration, and so the full scale will be nominally 9.8V after calibration. The calibration level is automatically stored on power-down. It should be noted
that the Analogue input 1 offset trim is included in the input voltage when the input voltage itself is used for calibration, but this trim is not included
when the internal reference is used for calibration.
7.26

T5/6 analogue input 1 sample time

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
Analogue input 1 is filtered using a window filter to remove quantisation noise and adjust the resolution of this input. The length of the window can be
adjusted with this parameter. The shortest possible window is 250µs. It should be noted that if this input is not used as a speed reference (Pr 1.36,
Pr 1.37) or as a hard speed reference ({Pr 3.22) the sample time affects the resolution. The nominal resolution is given by Pr 7.26 x 500 x 103,
therefore the default setting gives approximately 11 bit resolution.
128
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
1
0 to 3
0
Mode
VOLt
Voltage mode
0-20
0 - 20mA
4-20
4 - 20mA
H.Spd
High speed up date mode
FI
DE
Txt
VM
DP ND RA
0
FI
DE
Txt VM DP
ND
1
0 to 8.0 ms
4.0
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
Technical
Parameters
data
PS
1
1
PS
1
PS
1
1
Unidrive SP Regen Installation Guide
Component
Diagnostics
sizing
Issue Number: 2