Safety
Product
Introduction
Information
information
Trip
th
Motor thermistor trip
Check regen inductor temperature
24
Check thermistor continuity
Set Pr 7.15 = VOLt and reset the drive to disable this function
thS
Motor thermistor short circuit
Check regen inductor wiring
25
Replace regen inductor thermistor
Set Pr 7.15 = VOLt and reset the drive to disable this function
Unid.P
Power module unidentified trip
Check all interconnecting cables between power modules
110
Ensure cables are routed away from electrical noise sources
UP ACC
Onboard PLC program: cannot access Onboard PLC program file on drive
Disable drive - write access is not allowed when the drive is enabled
98
Another source is already accessing Onboard PLC program - retry once other action is complete
UP div0
Onboard PLC program attempted divide by zero
90
Check program
UP OFL
Onboard PLC program variables and function block calls using more than the allowed RAM space (stack overflow)
95
Check program
UP ovr
Onboard PLC program attempted out of range parameter write
94
Check program
UP PAr
Onboard PLC program attempted access to a non-existent parameter
91
Check program
UP ro
Onboard PLC program attempted write to a read-only parameter
92
Check program
UP So
Onboard PLC program attempted read of a write-only parameter
93
Check program
UP udf
Onboard PLC program un-defined trip
97
Check program
UP uSEr
Onboard PLC program requested a trip
96
Check program
UV
DC bus under voltage threshold reached
Check AC supply voltage level
Drive voltage rating (Vac)
1
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
Under voltage threshold (Vdc)
200
400
575
690
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
Diagnosis
175
350
435
435
Technical
Component
Parameters
data
sizing
Diagnostics
213