Baud Rate; Modbus Rtu Protocol; Minimum Comms Transmit Delay - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information

Modbus RTU protocol

Full details of the CT implementation of Modbus RTU are given in Chapter 7 Serial communications protocol in the Unidrive SP Advanced User
Guide.
The protocol provides the following facilities:
Drive parameter access with basic Modbus RTU
Drive parameter access via CMP extensions
Option module internal parameter access via CMP extensions
Access via an option module onto a network via CMP extensions (see specific Solutions Module User Guides for details)
Drive parameter database upload via CMP extensions
Drive Onboard PLC program upload/download via CMP extensions
The protocol supports access to 32 bit floating point parameters
The following product specific limitations apply:
Maximum slave response time when accessing the drive is 100ms
Maximum slave response time when accessing option module internal parameters or via an option module to a network may be longer than
100ms (see specific Solutions Module specifications for details)
Maximum number of 16 bit registers that can be written to, or read from, the drive itself is limited to 16
Maximum number of 16 bit registers that can be written to, or read from, a Solutions Module or via a Solutions Module - see Solutions Module
User Guide
The communications buffer can hold a maximum of 128bytes
Modbus RTU protocol, but with SM-Keypad Plus only
This setting is used for disabling comms access when the SM-Keypad Plus is used as a hardware key. See section 2.6.2 'Hardware key' feature in the
Unidrive SP Advanced User Guide for more information.
11.25

Baud rate

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
Used in all comms modes to define the baud rate.
Parameter value
String/baud rate
0
1
2
3
4
5
6
19200
7
38400
8*
57600
9*
115200
*Modbus RTU only
This parameter can be changed via the drive keypad, via a Solutions Module or via the comms interface itself. If it is changed via the comms
interface, the response to the command uses the original baud rate. The master should wait at least 20ms before sending a new message using the
new baud rate.
11.26

Minimum comms transmit delay

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
There will always be a finite delay between the end of a message from the host (master) and the time at which the host is ready to receive the
response from the drive (slave). The drive does not respond until at least 1ms after the message has been received from the host allowing 1ms for the
host to change from transmit to receive mode. This delay can be extended using Pr 11.26 if required for both ANSI and Modbus RTU protocols.
156
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
1
300
600
1200
2400
4800
9600
FI
DE
Txt VM DP
ND
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA NC NV
PT
US RW BU
1
0 to 9
6
RA NC NV
PT
US RW BU
1
0 to 250 ms
2
Technical
Component
Parameters
data
PS
1
1
PS
1
1
Unidrive SP Regen Installation Guide