General Trip Indications - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
Table 12-2 General trip indications
Trip
C.Acc
SMARTCARD trip: SMARTCARD Read / Write fail
Check SMARTCARD is fitted / located correctly
185
Replace SMARTCARD
C.Chg
SMARTCARD trip: Data location already contains data
Erase data in data location
179
Write data to an alternative data location
C.Cpr
SMARTCARD trip: The values stored in the drive and the values in the data block on the SMARTCARD are different
188
Press the red
C.dat
SMARTCARD trip: Data location specified does not contain any data
183
Ensure data block number is correct
C.Err
SMARTCARD trip: SMARTCARD data is corrupted
Ensure the card is located correctly
182
Erase data and retry
Replace SMARTCARD
C.Full
SMARTCARD trip: SMARTCARD full
184
Delete a data block or use different SMARTCARD
cL2
Analogue input 2 current loss (current mode)
28
Check analogue input 2 (terminal 7) current signal is present (4-20mA, 20-4mA)
cL3
Analogue input 3 current loss (current mode)
29
Check analogue input 3 (terminal 8) current signal is present (4-20mA, 20-4mA)
CL.bit
Trip initiated from the control word (Pr 6.42)
35
Disable the control word by setting Pr 6.43 to 0 or check setting of Pr 6.42
C.Optn
SMARTCARD trip: Solutions Modules fitted are different between source drive and destination drive
Ensure correct Solutions Modules are fitted
Ensure Solutions Modules are in the same Solutions Module slot
180
Press the red
C.rdo
SMARTCARD trip: SMARTCARD has the Read Only bit set
Enter 9777 in Pr xx.00 to allow SMARTCARD Read / Write access
181
Ensure card is not writing to data locations 500 to 999
SMARTCARD trip: SMARTCARD attempting to change the destination drive ratings
C.rtg
No drive rating parameters have been transferred
Press the red
Drive rating parameters are:
Parameter
4.05/6/7, 21.27/8/9
5.07, 21.07
5.09, 21.09
186
5.17, 21.12
5.23, 21.13
5.24, 21.14
5.25, 21.24
The above parameters will be set to their default values.
C.Typ
SMARTCARD trip: SMARTCARD parameter set not compatible with drive
Press the reset button
187
Ensure destination drive type is the same as the source parameter file drive type
dESt
Two or more parameters are writing to the same destination parameter
199
Set Pr xx.00 = 12001 check all visible parameters in the menus for duplication
EEPROM data corrupted - Drive mode becomes open loop and serial comms will timeout with remote keypad on the drive
EEF
RS485 comms port.
31
This trip can only be cleared by loading default parameters and saving parameters
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
reset button
reset button
reset button
Function
2.08
Standard ramp voltage
Current limits
Motor rated current
Motor rated voltage
Stator resistance
5.18
Switching frequency
Voltage offset
Transient inductance
Stator inductance
6.06
DC injection braking current
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
Diagnosis
Technical
Component
Parameters
data
sizing
Diagnostics