Motor connection

C is the AC cable length between the motoring drive and the motor.
Figure 4-5 Calculating the cable length of the regen system
Cable length B
±DC bus connections
Regen inductor
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
Electrical
design
installation
installation
Motor
www.controltechniques.com
Getting
Optimisation
Parameters
started
4.4.4

Cable length

The sum total length of the DC bus and motor cables (B and C in Figure
4-5) must not exceed the values shown in the table below:
Table 4-5 200V Regen system maximum cable lengths
200V Nominal AC supply voltage
Model
Maximum permissible cable length
3kHz
4kHz
SP1201
65m (210ft)
SP1202
100m (330ft)
SP1203
130m (425ft)
SP1204
SP2201
SP2202
200m
150m
(660ft)
(490ft)
SP2203
SP3201
SP3202
SP4201
65m
65m
SP4202
(210ft)
(210ft)
SP4203
SP5201
250m
185m
(820ft)
(607ft)
SP5202
SPMD1201
SPMD1202
250m
185m
(820ft)
(607ft)
SPMD1203
SPMD1204
Table 4-6 400V Regen system maximum cable lengths
400V Nominal AC supply voltage
Model
Maximum permissible cable length
3kHz
4kHz
SP1405
SP1406
SP2401
SP2402
200m
150m
SP2403
(660ft)
(490ft)
SP2404
SP3401
SP3402
SP3403
SP4401
SP4402
SP4403
SP5401
SP5402
SP6401
250m
185m
SP6402
(820ft)
(607ft)
SPMA1401
SPMA1402
SPMD1401
SPMD1402
SPMD1403
SPMD1404
Technical
Component
Diagnostics
data
sizing
6kHz
8kHz
12kHz
16kHz
(120ft)
50m
75m
(165ft)
100m
(245ft)
(330ft)
65m
65m
(210ft)
(210ft)
125m
90m
(410ft)
(295ft)
125m
(410ft)
6kHz
8kHz
12kHz
16kHz
100m
75m
50m
(120ft)
(330ft)
(245ft)
(165ft)
90m
(295ft)
125m
(410ft)
37m
37m
41