Component Data; Regen Inductors - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
10.4

Component data

The following parts may be used:
Motoring drive
Regen drive
Regen inductor
Softstart resistor
Switching frequency filter (optional)
EMC filter (optional)
Varistors
Fusing
Contactors
Overloads
In addition to the above the additional items are also required to
assemble a Unidrive SP Regen Brake Resistor replacement system:
Isolating transformer
DC bus diode
The internal EMC filter must be removed from drive.
CAUTION
Table 10-21 200V Regen inductor specifications
Inductor part
Amps
number
4401-0310
9.6
4401-0311
11.0
4401-0312
15.5
4401-0313
22
4401-0314
31
4401-0315
42
4401-0316
56
4401-0317
68
4401-0318
80
4401-0319
105
4401-0320
130
4401-0321
156
4401-0322
192
4401-0323
250
4401-0324
312
4401-0325
350
Table 10-22 400V Regen inductor specifications
Inductor part
Amps
number
4401-0001
9.5
4401-0002
12
4401-0003
16
4401-0004
25
4401-0005
34
4401-0006
40
4401-0007
46
4401-0008
60
4401-0009
70
4401-0010
96
4401-0011
124
4401-0012
156
4401-0013
180
4401-0014
200
4401-0015
300
4401-0205-00
350
196
System
Mechanical
design
installation
Losses
L
D
mH
W
mm
mm
3.5
71
215
180
2.7
72
215
180
2.2
116
215
180
1.6
157
215
180
1.10
193
270
180
0.81
200
270
200
0.6
264
325
220
0.5
299
325
220
0.4
298
325
220
0.32
338
370
260
0.26
394
375
280
0.22
475
395
280
0.18
526
395
280
0.14
610
430
300
0.11
776
430
300
0.10
863
490
320
Losses
L
D
mH
W
mm
mm
6.32
125.0
200
180
5.00
146.0
200
180
3.75
175.0
240
180
2.40
210.0
240
180
1.76
285.0
320
220
1.50
310.0
320
220
1.30
320.0
320
220
1.00
345.0
360
260
0.78
415.0
360
260
0.63
515.0
360
260
0.48
585.0
360
260
0.38
645.0
410
300
0.33
775.0
410
300
0.30
845.0
480
320
0.20
1760.0
480
320
0.16
1500
500
320
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
10.4.1

Regen inductors

NOTE
The regen inductor duty is very arduous, and therefore, correct
component selection is critical. The most sensitive aspect being the
inductor linearity. Only inductors specified in this installation guide
should be used.
The regen inductor supports the difference between the PWM voltage
from the Regen drive and the sinusoidal voltage from the supply. One
three-phase regen inductor is required per Regen drive.
Each regen inductor is fitted with a 170°C thermistor mounted in the
centre coil. The thermistor is set to 170°C at which point the resistance is
1000Ω, beyond 170°C a rapid rise in resistance will be seen.
The regen inductors have a normal operating temperature of
approximately 170°C depending upon the ambient and the
motor cable lengths. Care must be taken so that this does not
create a fire risk.
CAUTION
NOTE
If the permissible cable lengths are exceeded additional cooling may be
required for the regen inductors, refer to section 4.4.4 Cable length on
page 41.
H
Weight
Fixing centres (x * y)
mm
kg
200
10
120 x 140
200
11
120 x 140
200
12
120 x 140
200
15
120 x 140
240
17
160 x 140
240
24
160 x 160
320
32
200 x 180
320
33
200 x 180
320
39
200 x 180
360
55
240 x 220
360
65
240 x 240
360
77
240 x 240
360
97
240 x 240
410
110
280 x 260
410
120
280 x 260
480
130
320 x 260
H
Weight
Fixing centres (x * y)
mm
kg
215
12
120 x 140
215
14
120 x 140
270
17
160 x 140
270
24
160 x 160
325
32
200 x 180
325
33
200 x 180
325
39
200 x 180
370
55
240 x 220
370
65
240 x 240
370
75
240 x 240
370
95
240 x 240
430
110
280 x 260
430
120
280 x 260
490
130
320 x 260
490
140
320 x 240
570
165
320 x 260
Technical
Component
Parameters
data
Fixing
mm
mm
9
9
9
9
9
9
11
11
11
11
11
11
11
11
11
11
Fixing
mm
mm
9
9
9
9
11
11
11
11
11
11
11
11
11
11
11
11
Unidrive SP Regen Installation Guide
Diagnostics
sizing
Fixing
type
A
Fixing
type
A
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents