Pr 6.42 and Pr 6.43 provide a method of controlling the sequencer inputs and other functions directly from a single control word. If Pr 6.43 = 0 the
control word has no effect, if Pr 6.43 = 1 the control word is enabled. Each bit of the control word corresponds to a sequencing bit or function as
shown below.
Bits marked with * have no effect in regen mode.
Bit
Function
0
Drive enable
1*
Run forward
2*
Jog
3*
Run reverse
4*
Forward/reverse
5*
Run
6*
Not stop
7
Auto/manual
8*
Analogue/Preset reference
9*
Jog reverse
10
Reserved
11
Reserved
12
Trip drive
13
Reset drive
14
Keypad watchdog

Bits 0-7 and bit 9: sequencing control

When the control word is enabled (Pr 6.43 = 1), and the Auto/manual bit (bit7) are both one, bits 0 to 6 and bit 9 of the control word become active.
The equivalent parameters are not modified by these bits, but become inactive when the equivalent bits in the control word are active. When the bits
are active they replace the functions of the equivalent parameters. For example, if Pr 6.43 = 1 and bit 7 of Pr 6.42 = 1 the drive enable is no longer
controlled by Pr 6.15, but by bit 0 of the control word. If either Pr 6.43 = 0, or bit 7 of Pr 6.42 = 0, the drive enable is controlled by Pr 6.15.

Bit 8: Analogue/preset reference

When the control word is enabled (Pr 6.43) bit 8 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) The state
of bit 8 is written to Pr 1.42. With default drive settings this selects analogue reference 1 (bit8 = 0) or preset reference 1 (bit8 = 1). If any other drive
parameters are routed to Pr 1.42 the value of Pr 1.42 is undefined.
Bit12: Trip drive
When the control word is enabled (Pr 6.43) bit 12 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) When
bit 12 is set to one a CL.bit trip is initiated. The trip cannot be cleared until the bit is set to zero
Bit 13: Reset drive
When the control word is enabled (Pr 6.43) bit 13 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) When
bit 13 is changed from 0 to 1 the drive is reset. This bit does not modify the equivalent parameter (Pr 10.33).
Bit 14: Keypad watchdog
When the control word is enabled (Pr 6.43) bit 14 of the control word becomes active. (Bit 7 of the control word has no effect on this function.) A
watchdog is provided for an external keypad or other device where a break in the communication link must be detected. The watchdog system can be
enabled and/or serviced if bit 14 of the control word is changed from zero to one with the control word enabled. Once the watchdog is enabled it must
be serviced at least once every second or an "SCL" trip occurs. The watchdog is disabled when an "SCL" trip occurs, and so it must be re-enabled
when the trip is reset.
116
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
0 to 32,767
0
FI
DE
Txt VM DP
ND
0
Equivalent parameter
Pr 6.15
Pr 6.30
Pr 6.31
Pr 6.32
Pr 6.33
Pr 6.34
Pr 6.39
Pr 1.42
Pr 6.37
Pr 10.33
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
Technical
Component
Parameters
data
PS
1
1
PS
1
Unidrive SP Regen Installation Guide
Diagnostics
sizing
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents