Time Before Filter Change Due; Select Clock For Trip Log Time Stamping; Hardware Enable; Drive Event Flags - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
6.27

Time before filter change due

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
Background
See Pr 6.18 on page 113.
6.28

Select clock for trip log time stamping

Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
Background
The trip log includes time stamping for individual trips. If Pr 6.28 = 0, the powered-up clock is used for time stamping. If Pr 6.28 = 1, the run time clock
is used for time stamping. It should be noted that changing this parameter clears the trip and trip time logs.
6.29

Hardware enable

Drive mode
Regen
Bit
SP
Coding
1
Update rate
4ms
This bit is a duplicate of Pr 8.09 and reflects the state of the enable input. If the destination of one of the drive digital I/O (Pr 8.21 to Pr 8.26) is set to
Pr 6.29 and the I/O is set as an input the state of the input does not affect the value of this parameter as it is protected, however, it does provide a fast
disable function. The secure disable input to the drive (T31) disables the drive in hardware by removing the gate drive signals from the inverter IGBT's
and also disables the drive via the software system. When the drive is disabled by de-activating the secure disable input there can be a delay of up to
20ms. However, if a digital I/O is set up to provide the fast disable function it is possible to disable the drive within 600µs of de-activating the input. To
do this the enable signal should be connected to both the secure disable (T31) and to the digital I/O selected for the fast disable function. The state of
the digital I/O including the effect of its associated invert parameter is ANDed with the secure disable to enable the drive.
If the safety function of the Secure Disable input is required then there must not be a direct connection between the Secure Disable input (T31) and
any other digital I/O on the drive. If the safety function of the Secure Disable input and the fast disable function is required then the drive should be
given two separate independent enable signals. A safety related enable from a safe source connected to the Secure Disable input on the drive. A
second enable connected to the digital I/O on the drive selected for the fast disable function. The circuit must be arranged so that a fault which causes
the fast input to be forced high cannot cause the Secure Disable input to be forced high, including the case where a component such as a blocking
diode has failed.
6.41

Drive event flags

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Default
Regen
Update rate
Background
The drive event flags indicate certain actions have occurred within the drive as described below.
Defaults loaded (Bit 0)
The drive sets bit 0 when defaults have been loaded and the associated parameter save has been completed. The drive does not reset this flag
except at power-up. This flag is intended to be used by SM-Applications option module programs to determine when the default loading process is
complete. For example an application may require defaults that are different from the standard drive defaults. These may be loaded and another
parameter save initiated by the SM-Applications module when this flag is set. The flag should then be cleared so that the next event can be detected.
Drive mode changed (Bit 1)
The drive sets bit 1 when the drive mode has changed and the associated parameter save has been completed. The drive does not reset this flag
except at power-up. This flag is intended to be used in a similar way as bit 0.
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
FI
DE
Txt VM
DP
ND
1
0 to 30,000 hrs
FI
DE
Txt
VM
DP
ND
0
FI
DE
Txt
VM DP
ND
FI
DE
Txt VM
DP
ND
0 to 65535
0
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
Technical
Parameters
data
PS
1
1
PS
1
PS
PS
1
1
Component
Diagnostics
sizing
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents