Drive Enable Mode Select; T24 Digital I/O 1 Invert; T22 24V Output Source Invert - Emerson SP1201 Installation Manual

Unidrive sp regen series 200v 400v 575v 690v
Table of Contents

Advertisement

Safety
Product
Introduction
Information
information
8.01
T24 digital I/O 1 state
8.02
T25 digital I/O 2 state
8.03
T26 digital I/O 3 state
8.04
T27 digital input 4 state
8.05
T28 digital input 5 state
8.06
T29 digital input 6 state
8.07
Relay status
8.08
T22 24V output state
8.09
Drive enable indicator
Drive mode
Regen
Bit
SP
Coding
1
Update rate
4ms
8.10

Drive enable mode select

Drive mode
Regen
Coding
Bit
SP
1
Default
Regen
Update rate
Background read
Unidrive SP has a dedicated hardware enable input which always controls Pr 6.29. If the enable is inactive the IGBT firing signals are turned off
without software intervention. As default (Pr 8.10 = 0) the drive is in the inhibit mode when the enable is inactive. Setting this parameter to one causes
the enable to behave as an Et trip input. When the input becomes inactive an Et trip is initiated. This does not affect Pr 10.32 (Et trip parameter),
therefore an Et trip can be initiated in this mode either by making the enable inactive or setting Pr 10.32 to one.
8.11

T24 digital I/O 1 invert

8.12
T25 digital I/O 2 invert
8.13
T26 digital I/O 3 invert
8.14
T27 digital input 4 invert
8.15
T28 digital input 5 invert
8.16
T29 digital input 6 invert
8.17
Relay source invert
8.18

T22 24V output source invert

Drive mode
Regen
Bit
SP
Coding
1
Default
Regen
Update rate
4ms
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
1
FI
DE
Txt VM DP
ND
OFF (0)
FI
DE
Txt VM DP
ND
Pr 8.11 to Pr 8.17 = OFF (0), Pr 8.18 = On (1)
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
RA NC NV
PT
US RW BU
1
Technical
Component
Parameters
data
PS
PS
1
PS
1
Diagnostics
sizing
135

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents