7.01

T5/6 analogue input 1 level

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
4ms
This input operates in voltage mode only where -9.8V and +9.8V at the input correspond with -100.0% and 100.0% respectively in this parameter.
7.02
T7 analogue input 2 level
7.03

T8 analogue input 3 level

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
4ms
These inputs can operate in different modes defined by Pr 7.11 and Pr 7.15.
In current modes (modes 0 to 5) the minimum and maximum current values given in mA correspond with 0.0% and 100.0% respectively in Pr 7.02
and Pr 7.03. Therefore in modes 2 and 4 the parameter is at 0.0% when the input current is less than 4mA, and in modes 3 and 5 the parameter is at
100.0% when the input current is less than 4mA.
In voltage mode (mode 6) -9.8V and +9.8V at the input correspond with -100.0% and 100.0% respectively in Pr 7.02 and Pr 7.03.
When analogue input 3 is in thermistor mode (modes 7 to 9) the display indicates the resistance of the thermistor as a percentage of 10kΩ
7.04

Power circuit stack temperature 1

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
Background
7.05
Power circuit stack temperature 2
Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
Background
7.06

Control board temperature

Drive mode
Regen
Bit
SP
Coding
Range
Regen
Update rate
Background
For drive sizes SP1xxx to SP5xxx two temperatures are available from the power circuit, and these are displayed in Pr 7.04 and Pr 7.05. For drive
sizes SP0xxx, SP6xxx and SPMxxxx three temperatures are available from the power circuit, and these are displayed in Pr 7.04, Pr 7.05 and Pr 7.36.
If SPMxxxx drives consist of more that one parallel power module the temperatures displayed are the highest value from any of the parallel modules.
If the temperature displayed in Pr 7.04, Pr 7.05 or Pr 7.36 exceeds the trip threshold for the parameter, the drive does not have parallel power
modules and is not a single power module that uses the parallel power module hardware, an Oht2 trip is initiated. This trip can only be reset if the
parameter that has caused the trip falls below the trip reset level. If the temperature exceeds the alarm level a "hot" alarm is displayed. If the
temperature for any of these monitoring points is outside the range -20°C to 150°C it is assumed that the monitoring thermistor has failed and a
hardware fault trip is initiated (Pr 7.04 - HF27, Pr 7.05 and Pr 7.36 - HF28).
122
System
Mechanical
design
installation
FI
DE
Txt VM DP
ND
2
1
±100.00 %
FI
DE
Txt VM DP
ND
1
1
±100.0 %
FI
DE
Txt VM DP
ND
1
-128 to 127
FI
DE
Txt VM DP
ND
1
-128 to 127
FI
DE
Txt VM DP
ND
1
-128 to 127
www.controltechniques.com
Electrical
Getting
Optimisation
installation
started
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
o
C
RA
NC
NV
PT
US RW BU
1
1
o
C
RA
NC
NV
PT
US RW BU
1
1
o
C
Technical
Component
Parameters
data
sizing
PS
PS
PS
PS
PS
1
Unidrive SP Regen Installation Guide
Diagnostics
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents