6.3

Cable and fuse ratings

The input current is affected by the supply voltage and impedance.
Typical input current
The values of typical input current are given to aid calculations for power
flow and power loss.
The values of typical input current are stated for a balanced supply.
Maximum continuous input current
The values of maximum continuous input current are given to aid the
selection of cables and fuses. These values are stated for the worst case
condition with the unusual combination of stiff supply with bad balance.
The value stated for the maximum continuous input current would only
be seen in one of the input phases. The current in the other two phases
would be significantly lower.
The values of maximum input current are stated for a supply with a 2%
negative phase-sequence imbalance and rated at the maximum supply
fault current given in Table 6-2 to Table 6-2.
Table 6-2 Size 1 to 3 input current, fuse and cable size ratings
Maximum
continuous
Fuse
Model
input
rating
current
IEC gG
A
A
SP1201
5.2
10
SP1202
6.8
10
SP1203
9.6
12
SP1204
11
12
SP2201
15.5
20
SP2202
22
25
SP2203
28
32
SP3201
42
50
SP3202
54
63
SP1405
8.8
12
SP1406
11
16
SP2401
15.3
20
SP2402
21
25
SP2403
29
32
SP2404
29
32
SP3401
35
40
SP3402
43
50
SP3403
56
63
SP3501
5.4
8
SP3502
6.1
8
SP3503
8.4
12
SP3504
11
12
SP3505
16
20
SP3506
22
25
SP3507
27
32
Unidrive SP Regen Installation Guide
Issue Number: 2
System
Mechanical
design
installation
installation
European
USA
Cable size
Fuse
EN60204
rating
UL508C
IEC gG
Input
A
2
mm
1.0
10
1.0
10
1.0
12
1.0
12
2.5
20
4.0
25
6.0
32
16
50
25
63
1.0
15
1.5
15
2.5
20
4.0
25
6.0
30
6.0
30
10
40
16
45
25
60
1.0
8
1.0
8
1.0
12
1.0
12
2.5
20
4.0
25
6.0
32
www.controltechniques.com
Electrical
Getting
Optimisation
started
Cable
size
Input
AWG
18
16
14
14
14
10
8
16
25
14
14
14
10
8
8
6
6
4
18
16
14
14
14
10
8
Technical
Component
Parameters