Cubicle design and drive ambient
temperature
Drive derating is required for operation in high ambient temperatures
(derating information is provided in the Unidrive SP User Guide).
Totally enclosing or through panel mounting the drive in either a sealed
cabinet (no airflow) or in a well ventilated cabinet makes a significant
difference on drive cooling.
The chosen method affects the ambient temperature value (T
should be used for any necessary derating to ensure sufficient cooling
for the whole of the drive.
The ambient temperature for the four different combinations is defined
below:
1. Totally enclosed with no air flow (<2 m/s) over the drive
T
= T
+ 5°C
rate
int
2. Totally enclosed with air flow (>2 m/s) over the drive
T
= T
rate
int
3. Through panel mounted with no airflow (<2 m/s) over the drive
T
= the greater of T
+5°C, or T
rate
ext
4. Through panel mounted with air flow (>2 m/s) over the drive
T
= the greater of T
or T
rate
ext
Where:
T
= Temperature outside the cabinet
ext
T
= Temperature inside the cabinet
int
T
= Temperature used to select current rating from tables in
rate
Chapter 10 Technical data on page 183.
Regen inductors can produce significant losses with a normal
operating temperature in the region of 150°C dependant
upon the ambient temperature. Location of the regen
inductors should be considered to prevent damage to heat
CAUTION
sensitive components or create a fire risk.
64
System
Mechanical
design
installation
installation
rate
int
int
www.controltechniques.com
Electrical
Getting
Optimisation
started
) which
Technical
Component
Parameters
data
sizing
Unidrive SP Regen Installation Guide
Issue Number: 2
Diagnostics

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents