Parame-
ter Num-
Name
ber
Sets P-control proportional gain.
Proportional
b5-02
P-control is not performed when the set-
gain (P)
ting is 0.00.
Sets I-control integral time.
b5-03
Integral (I) time
I-control is not performed when the set-
ting is 0.0.
Sets the I-control limit as a percentage of
b5-04
Integral (I) limit
the maximum output frequency.
Sets the limit after PI-control as a per-
b5-06
PI limit
centage of the maximum output fre-
quency.
Sets the offset after PI-control as a per-
PI offset adjust-
b5-07
centage of the maximum output fre-
ment
quency.
Sets the time constant for low pass filter
PI delay time
b5-08
for PI-control output.
constant
Usually not necessary to set.
Selects forward/reverse direction for PI
PI output char-
output.
b5-09
acteristics selec-
0: PI output is forward.
tion
1: PI output is reverse
b5-10
PI output gain
Sets output gain.
0: Limit to 0 when PI output is negative.
1: Reverses when PI output is negative.
PI reverse out-
b5-11
Limit to 0 is also active when reverse
put selection
prohibit is selected by
b1-04.
0: No detection of PI feedback loss.
1: Detection of PI feedback loss.
Selection of PI
Operation continues during detection,
b5-12
feedback signal
the fault contact is not operated.
loss detection
2: Detection of PI feedback loss.
The motor coasts to stop at detection,
and the fault contact operates.
Sets the PI feedback loss detection level
PI feedback loss
b5-13
as percentage using the maximum output
detection level
frequency as 100%.
PI feedback loss
b5-14
Sets the PI feedback loss detection time.
detection time
Sleep function
Sets the sleep function start level as a fre-
b5-15
operation level
quency.
Sleep operation
Sets the delay time until the sleep func-
b5-16
delay time
tion starts.
Accel/decel
Sets the accel/decel time for the PI Soft-
b5-17
time for PI ref-
starter (SFS).
erence
PI Setpoint
0: Disabled
b5-18
Selection
1: Enabled
b5-19
PI Setpoint
PI-target value
Setting
Description
Range
0.00
to
25.00
0.0 to
360.0
0.0 to
100.0
0.0 to
100.0
-100.0
to
+100.0
0.00 to
10.00
0 or 1
0.0 to
25.0
0 or 1
0 to 2
0 to
100
0.0 to
25.5
0.0 to
200.0
0.0 to
25.5
0.0 to
25.5
0 to 1
0.00 to
100.00
%
Change
MEMO-
Factory
during
Access
BUS
Setting
Opera-
Level
Register
tion
1.00
Yes
A
1A6H
1.0 s
Yes
A
1A7H
100.0%
Yes
A
1A8H
100.0%
Yes
A
1AAH
0.0%
Yes
A
1ABH
0.00 s
Yes
A
1ACH
0
No
A
1ADH
1.0
No
A
1AEH
0
No
A
1AFH
0
No
A
1B0H
0%
No
A
1B1H
1.0 s
No
A
1B2H
0.0 Hz
No
A
1B3H
0.0 s
No
A
1B4H
0.0 s
No
A
1B5H
0
No
A
1DCH
0
Yes
A
1DDH
5
5
5-