Using an Emergency Stop
Set a multi-function input terminal (H1-
deceleration time set in C1-09. If inputting the emergency stop with an NO contact, set the multi-function
input terminal (H1-
input terminal (H1-
After the emergency stop command has been input, operation cannot be restarted until the Inverter has
stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.
Related parameters
Param-
eter
Number
C1-09
Emergency stop time
6
14
6-
) to 15, and if inputting the emergency stop with an NC contact, set the multi-function
) to 17.
Name
Sets the deceleration time when the multi-function
input "Emergency (fast) stop" is ON.
This time will be used when a fault is detected, for
which emergency stop was programmed as stop-
ping method.
) to 15 or 17 (emergency stop) to decelerate to stop using the
Description
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.0 to
10.0 s
No
A
6000.0