Writing Parameter Set Values Stored in the Digital Operator to the Inverter (COPY)
To write parameter set values stored in the Digital Operator to the Inverter, use the following method.
Step
No.
1
2
3
4
5
6
6
7
If an error is displayed, set the parameters again. Error displays and their meanings are shown below. (Refer to
Chapter 7, Errors when Using the Digital Operator Copy
Error Display
108
6-
Digital Operator Display
Inverter product code or Inverter software number are different.
Inverter capacity with which you are trying to copy, and the Inverter capacity stored in the Digital Operator are
different.
Comparison between the parameter written to the Inverter and the parameter in the Digital Operator are different.
After copying has ended, comparison between the checksum value of the Inverter parameter area and the check-
sum value of the Digital Operator parameter area are different.
Explanation
Press the MENU key, and select advanced program-
ming mode.
Press the DATA/ENTER key to enter the program-
ming mode.
Select parameter o3-01 (Copy Function Selection)
using the Increment key and Decrement key.
Press the DATA/ENTER key to enter the parameters
setting display.
Change the set value to 2 using the Increment key.
Press the DATA/ENTER key. The COPY function
will start.
If the COPY function ends normally, "End" is dis-
played on the Digital Operator. Parameter o3-01 is
automatically reset to 0, and then the display returns
to o3-01.
Function.)
Meaning